Liebert Foundation Mounting
—Two 1/4-20 cage nuts on the underside of module allow direct
attachment to any Liebert Foundation cabinet; bolts provided with Liebert XDV module.
•
Mounting Clips for Non-Liebert Cabinets
—The Liebert XDV module is supplied with mounting
clips that allow attachment to a non-Liebert cabinet (some drilling may be required).
4.16 Optional Features—Liebert XDV
•
Refrigerant Pre-Charge
—The Liebert XDV can be precharged with refrigerant. The module
will have the one-shot fittings and will be pressurized. The one-shot Liebert XD Flex Piping will
also be precharged with refrigerant.
•
External Mounting Brackets
—The Liebert XDV can be suspended from the overhead building
structure. The external mounting brackets are ship-loose items.
•
Field-Installed Flexible Piping
(for use with prefabricated piping assemblies)—Field-installed
flexible piping kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8, 2.4 and 3 meters).
Connection style to the module end may be straight or 90 degrees with one-shot or removable
connections. Flex pipes with one-shot connections will have pressurized R134a. Flex pipes with
removable connections will have a low pressure nitrogen charge Connection to the
prefabricated piping assembly is with a threaded coupler. For information on acquiring the
correct kit for your installation, refer to DPN000781, available from Liebert by calling 1-800-
LIEBERT and from your local Vertiv representative.
•
Smart Module
—Liebert XDV smart modules allow remote shutdown, fan failure alarms and
automatically switching the second fan On and Off. This saves energy by permitting the
module to run with one fan and switching on a second fan when the temperature requires both
fans for cooling. Liebert XD smart modules are able to provide alarm conditions such as fan
failure or condensate detection at the Liebert XDP display via CANbus communication. For
electrical connection details, refer to the Liebert XDV user manual, SL-16626, available on the
Vertiv web site: www.VertivCo.com
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
87
Содержание Liebert XD Series
Страница 1: ...Liebert Xtreme Density System Design Manual...
Страница 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Страница 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Страница 45: ...Figure 3 22 Liebert XD return header orientation Vertiv Liebert Xtreme Density System Design Manual 45...
Страница 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Страница 76: ...Figure 4 12 Liebert XDO internal mounting location Vertiv Liebert Xtreme Density System Design Manual 76...
Страница 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Страница 90: ...Figure 4 23 Suspending single Liebert XDV from Unistruts Vertiv Liebert Xtreme Density System Design Manual 90...
Страница 103: ...Figure 5 4 Piping locations floor stand and valve assembly Vertiv Liebert Xtreme Density System Design Manual 103...
Страница 112: ...Figure 5 16 Front view of Liebert XDP and electrical enclosure Vertiv Liebert Xtreme Density System Design Manual 112...
Страница 115: ...Figure 5 19 Liebert XDP high voltage connections 60Hz Vertiv Liebert Xtreme Density System Design Manual 115...
Страница 116: ...Figure 5 20 Liebert XDP high voltage connections 50Hz Vertiv Liebert Xtreme Density System Design Manual 116...
Страница 120: ...Figure 6 2 Condenser planning dimensional data Six fan units Vertiv Liebert Xtreme Density System Design Manual 120...
Страница 121: ...Figure 6 3 Typical condenser footprint dimensions Vertiv Liebert Xtreme Density System Design Manual 121...
Страница 138: ...Figure 6 13 Drycooler planning dimensional data Eight fan units Vertiv Liebert Xtreme Density System Design Manual 138...
Страница 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Страница 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Страница 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Страница 170: ...Figure 7 11 CAN Isolator location within the Liebert XDP XDC Vertiv Liebert Xtreme Density System Design Manual 170...
Страница 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Страница 198: ...Figure 9 7 Liebert XDP model number nomenclature Vertiv Liebert Xtreme Density System Design Manual 198...
Страница 199: ......