7.9.2 CANbus Maximum Length
The CANbus network (the sum of the two CANbus chains) has a maximum length limitation.
•
If the Liebert XDP or Liebert XDC with iCOM does not have a CAN Isolator, the maximum
distance is 150 ft. (46m) total network without measuring the final device voltage. The 150 ft.
(46m) total must also include the remote temperature and humidity sensor cable lengths.
•
If the Liebert XDP or Liebert XDC contains a CAN Isolator, the maximum distance is 300 ft.
(91m). To exceed this length, the final device voltage must be measured.
7.10 CANbus Cables
The Liebert XDP may be connected to the Smart Modules with a CANbus cable. The shielded cable
consists of three pairs of twisted wires with a 6-pin RJ12 connector.
NOTICE
Risk of improper wiring. Can cause equipment damage.
Mismatching wire pins at the RJ12 connection will damage the CAN device. Extreme caution should be
taken when making cables.
Figure 7.9 CANbus cable
Liebert Part #
Dimension A ft. (m)
300157G1
6 (1.8)
300157G2
10 (3)
300157G3
20 (6)
300157G4
30 (9.1)
300157G5
60 (18.3)
300157G6
90 (27.4)
300157G7
120 (36.6)
300157G8
150 (45.7)
300157G9
6.25 (1.9)
300157G10
3 (0.9)
Table 7.3 CANbus cable lengths and part numbers
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
168
Содержание Liebert XD Series
Страница 1: ...Liebert Xtreme Density System Design Manual...
Страница 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Страница 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Страница 45: ...Figure 3 22 Liebert XD return header orientation Vertiv Liebert Xtreme Density System Design Manual 45...
Страница 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Страница 76: ...Figure 4 12 Liebert XDO internal mounting location Vertiv Liebert Xtreme Density System Design Manual 76...
Страница 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Страница 90: ...Figure 4 23 Suspending single Liebert XDV from Unistruts Vertiv Liebert Xtreme Density System Design Manual 90...
Страница 103: ...Figure 5 4 Piping locations floor stand and valve assembly Vertiv Liebert Xtreme Density System Design Manual 103...
Страница 112: ...Figure 5 16 Front view of Liebert XDP and electrical enclosure Vertiv Liebert Xtreme Density System Design Manual 112...
Страница 115: ...Figure 5 19 Liebert XDP high voltage connections 60Hz Vertiv Liebert Xtreme Density System Design Manual 115...
Страница 116: ...Figure 5 20 Liebert XDP high voltage connections 50Hz Vertiv Liebert Xtreme Density System Design Manual 116...
Страница 120: ...Figure 6 2 Condenser planning dimensional data Six fan units Vertiv Liebert Xtreme Density System Design Manual 120...
Страница 121: ...Figure 6 3 Typical condenser footprint dimensions Vertiv Liebert Xtreme Density System Design Manual 121...
Страница 138: ...Figure 6 13 Drycooler planning dimensional data Eight fan units Vertiv Liebert Xtreme Density System Design Manual 138...
Страница 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Страница 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Страница 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Страница 170: ...Figure 7 11 CAN Isolator location within the Liebert XDP XDC Vertiv Liebert Xtreme Density System Design Manual 170...
Страница 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Страница 198: ...Figure 9 7 Liebert XDP model number nomenclature Vertiv Liebert Xtreme Density System Design Manual 198...
Страница 199: ......