Refrigerant Return
to Liebert XDP/Liebert XDC
7/8" OD, Copper
Serviceable Parts
Fan and electrical components
Exterior Finish – Bottom, Sides, Front and
Rear
Black, matte finish, heat-fused powder coat
Exterior Finish - Top
Hot-dipped galvanized steel
Agency
Approvals
CSA 60 Hz
CSA 60Hz
CE 50Hz
1. Refer to Figure 9.3 on the next page for full part number.
Table 9.4 Liebert XDO16 specifications (continued)
Models
XDO20BK
1
XDO20SK
1
XDO20BS
1
XDO20SS
1
60Hz
60Hz
50Hz
Cooling Capacity
Nominal (92°F [33°C] EAT): 20kW / 5.7 Tons
Maximum (100°F [38°C] EAT): 23.1kW / 6.6 Tons
Nominal (92°F [33°C] EAT): 17.7kW / 5 Tons
Maximum (103°F [39°C] EAT): 23.1kW / 6.6
Tons
Conditions
Capacity rating is @ 55ºF (13°C) Entering Fluid Temperature and 50ºF (10°C) or lower dew point
Electrical Requirements
Input Voltage
1ph-60Hz-120V
1ph-60Hz-220-240V
1ph-50Hz-220-240V
Input Power Connections
Terminal blocks provided internal to module
Full Load Amps
2.7A @ 120V
1.64A @ 230V
1.64A @ 230V
Wire Size Amps
3.4
2.0
2.0
Overcurrent Protection Device
15
15
15
Power consumption,
nominal, watts
335
350
350
Dimensions, inches (mm)
Length
72-1/4 (1835)
Width
24-1/8 (613)
Height
22-1/2 (572) not including electrical and piping access
Weight, lb (kg)
Module only
150 (68)
Shipping weight
238 (108)
296 (134)
Installed, with refrigerant, without options
155 (70)
Number of Fans
1
1
1
Airflow, Nominal, ft3/ min (m3/ hr)
2700 (4590)
2250 (3820)
Audible Noise
85 dBa sound power
83 dBa sound power
Pipe Connections (without flex pipe)
Refrigerant Supply
from Liebert XDP/Liebert XDC
1/2" OD, Copper
Table 9.5 Liebert XDO20 specifications
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
187
Содержание Liebert XD Series
Страница 1: ...Liebert Xtreme Density System Design Manual...
Страница 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Страница 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Страница 45: ...Figure 3 22 Liebert XD return header orientation Vertiv Liebert Xtreme Density System Design Manual 45...
Страница 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Страница 76: ...Figure 4 12 Liebert XDO internal mounting location Vertiv Liebert Xtreme Density System Design Manual 76...
Страница 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Страница 90: ...Figure 4 23 Suspending single Liebert XDV from Unistruts Vertiv Liebert Xtreme Density System Design Manual 90...
Страница 103: ...Figure 5 4 Piping locations floor stand and valve assembly Vertiv Liebert Xtreme Density System Design Manual 103...
Страница 112: ...Figure 5 16 Front view of Liebert XDP and electrical enclosure Vertiv Liebert Xtreme Density System Design Manual 112...
Страница 115: ...Figure 5 19 Liebert XDP high voltage connections 60Hz Vertiv Liebert Xtreme Density System Design Manual 115...
Страница 116: ...Figure 5 20 Liebert XDP high voltage connections 50Hz Vertiv Liebert Xtreme Density System Design Manual 116...
Страница 120: ...Figure 6 2 Condenser planning dimensional data Six fan units Vertiv Liebert Xtreme Density System Design Manual 120...
Страница 121: ...Figure 6 3 Typical condenser footprint dimensions Vertiv Liebert Xtreme Density System Design Manual 121...
Страница 138: ...Figure 6 13 Drycooler planning dimensional data Eight fan units Vertiv Liebert Xtreme Density System Design Manual 138...
Страница 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Страница 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Страница 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Страница 170: ...Figure 7 11 CAN Isolator location within the Liebert XDP XDC Vertiv Liebert Xtreme Density System Design Manual 170...
Страница 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Страница 198: ...Figure 9 7 Liebert XDP model number nomenclature Vertiv Liebert Xtreme Density System Design Manual 198...
Страница 199: ......