4.6 Optional Features—Liebert XDH
•
Smart Module
—Smart modules will allow remote shutdown, fan failure alarms and automatically
switching the second fan bank On and Off. The controls save energy by permitting the module
to turn one fan in each fan bank Off based on the supply and return temperature. Liebert XD
smart modules are able to provide alarm conditions such as fan failure or condensate detection
at the Liebert XDP display via CANbus communication. For electrical connection details, refer
to the Liebert XDH user manual, SL-17210, available on the Vertiv web site: www.VertivCo.com
•
Refrigerant Precharge
—The Liebert XDH can be precharged with refrigerant. The module will
have one-shot fittings and will be pressurized. The one-shot Liebert XD Flex Piping will also be
precharged with refrigerant.
•
Field-Installed Flexible Piping
(for use with prefabricated piping assemblies)—Field-installed
flexible piping kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8, 2.4 and 3 meters).
Connection style to the module end may be straight or 90 degrees with one-shot style
couplings or removable couplings. Flex pipes with one-shot connections will have pressurized
R134a. Flex pipes with removable connections will have a low pressure nitrogen charge
Connection to the prefabricated piping assembly is with a threaded coupler. For information on
acquiring the correct kit for your installation, refer to DPN000780, available by calling 1-800-
LIEBERT and from your local Vertiv representative.
•
Tie-Down Bracket
—An optional tie-down bracket may be installed on the Liebert XDH to
secure it in the row. The bracket keeps space between the Liebert XDH and adjacent
equipment constant, preventing vibration.
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
69
Содержание Liebert XD Series
Страница 1: ...Liebert Xtreme Density System Design Manual...
Страница 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Страница 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Страница 45: ...Figure 3 22 Liebert XD return header orientation Vertiv Liebert Xtreme Density System Design Manual 45...
Страница 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Страница 76: ...Figure 4 12 Liebert XDO internal mounting location Vertiv Liebert Xtreme Density System Design Manual 76...
Страница 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Страница 90: ...Figure 4 23 Suspending single Liebert XDV from Unistruts Vertiv Liebert Xtreme Density System Design Manual 90...
Страница 103: ...Figure 5 4 Piping locations floor stand and valve assembly Vertiv Liebert Xtreme Density System Design Manual 103...
Страница 112: ...Figure 5 16 Front view of Liebert XDP and electrical enclosure Vertiv Liebert Xtreme Density System Design Manual 112...
Страница 115: ...Figure 5 19 Liebert XDP high voltage connections 60Hz Vertiv Liebert Xtreme Density System Design Manual 115...
Страница 116: ...Figure 5 20 Liebert XDP high voltage connections 50Hz Vertiv Liebert Xtreme Density System Design Manual 116...
Страница 120: ...Figure 6 2 Condenser planning dimensional data Six fan units Vertiv Liebert Xtreme Density System Design Manual 120...
Страница 121: ...Figure 6 3 Typical condenser footprint dimensions Vertiv Liebert Xtreme Density System Design Manual 121...
Страница 138: ...Figure 6 13 Drycooler planning dimensional data Eight fan units Vertiv Liebert Xtreme Density System Design Manual 138...
Страница 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Страница 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Страница 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Страница 170: ...Figure 7 11 CAN Isolator location within the Liebert XDP XDC Vertiv Liebert Xtreme Density System Design Manual 170...
Страница 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Страница 198: ...Figure 9 7 Liebert XDP model number nomenclature Vertiv Liebert Xtreme Density System Design Manual 198...
Страница 199: ......