Models
XDV8BK*
XDV8SK*
XDV8BT*
XDV8ST*
XDV8BS*
XDV8SS*
60 Hz
60 Hz
50 Hz
50 Hz
Depth – Bottom
29-5/8 (752)
Weight, lb (kg)
Module only
77 (35)
Shipping weight
125 (57)
Installed, with refrigerant
79 (36)
Number of Fans
2
2
2
2
Airflow, Nominal,
ft3/ min (m3/ hr)
1000 (1699) with rear inlet.
Bottom inlet airflow may be less,
depending on restrictions inside cabinet
833 (1415) with rear inlet.
Bottom inlet airflow may be less,
depending on restrictions inside cabinet
Audible noise
78 dBa sound power
73 dBa sound power
Pipe Connections (without Liebert Flex Pipe)
Refrigerant Supply
from Liebert XDP/Liebert XDC
1/2" OD Cu, (optional 1/2" threaded coupler flex piping)
Refrigerant Return
to Liebert XDP/Liebert XDC
5/8" OD Cu, (optional 3/4" threaded coupler flex piping)
Serviceable Parts
Fans and electrical components
Cabinet Exterior Finish
Black, matte finish, heat-fused powder coat
Options
Smart Module control board (factory-installed)
Dry contact, 24VAC, 1A maximum
Pre-Charged Refrigerant
R-134a refrigerant, one-shot connections
Agency
Approvals
CSA 60Hz
CSA 50Hz
CE 50Hz
*Refer to Figure 9.5 on page 193 for complete part number.
Table 9.10 Liebert XDV8 specifications (continued)
Models
XDV10BK*
XDV10SK*
XDV10BT*
XDV10ST*
XDV10BS*
XDV10SS*
60 Hz
60 Hz
50 Hz
50 Hz
Cooling Capacity
Nominal (98ºF [37ºC] EAT: 10kW / 2.8 Tons
Maximum (106ºF [41ºC] EAT): 11.7kW/3.3 Tons
Nominal (98ºF [37ºC] EAT): 8.3kW / 2.4 Tons
Maximum (116ºF [47ºC] EAT): 11.7kW/3.3 Tons
Conditions
Capacity Rating is @ 55ºF (13ºC) Entering Fluid Temperature and
50ºF (10ºC) or lower dew point, rear air inlet.
Electrical Requirements
Input
120V model: 1ph-60 Hz
230V model: 1ph-60 Hz
230V model: 1ph-50 Hz
Input power connections
2 power connections, each model
Full Load Amps
120V model: 2.0A
230V model: 1.0A
Table 9.11 Liebert XDV10 specifications
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
191
Содержание Liebert XD Series
Страница 1: ...Liebert Xtreme Density System Design Manual...
Страница 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Страница 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Страница 45: ...Figure 3 22 Liebert XD return header orientation Vertiv Liebert Xtreme Density System Design Manual 45...
Страница 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Страница 76: ...Figure 4 12 Liebert XDO internal mounting location Vertiv Liebert Xtreme Density System Design Manual 76...
Страница 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Страница 90: ...Figure 4 23 Suspending single Liebert XDV from Unistruts Vertiv Liebert Xtreme Density System Design Manual 90...
Страница 103: ...Figure 5 4 Piping locations floor stand and valve assembly Vertiv Liebert Xtreme Density System Design Manual 103...
Страница 112: ...Figure 5 16 Front view of Liebert XDP and electrical enclosure Vertiv Liebert Xtreme Density System Design Manual 112...
Страница 115: ...Figure 5 19 Liebert XDP high voltage connections 60Hz Vertiv Liebert Xtreme Density System Design Manual 115...
Страница 116: ...Figure 5 20 Liebert XDP high voltage connections 50Hz Vertiv Liebert Xtreme Density System Design Manual 116...
Страница 120: ...Figure 6 2 Condenser planning dimensional data Six fan units Vertiv Liebert Xtreme Density System Design Manual 120...
Страница 121: ...Figure 6 3 Typical condenser footprint dimensions Vertiv Liebert Xtreme Density System Design Manual 121...
Страница 138: ...Figure 6 13 Drycooler planning dimensional data Eight fan units Vertiv Liebert Xtreme Density System Design Manual 138...
Страница 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Страница 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Страница 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Страница 170: ...Figure 7 11 CAN Isolator location within the Liebert XDP XDC Vertiv Liebert Xtreme Density System Design Manual 170...
Страница 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Страница 198: ...Figure 9 7 Liebert XDP model number nomenclature Vertiv Liebert Xtreme Density System Design Manual 198...
Страница 199: ......