Refrigerant R-407C uses a POE (polyolester) lubricant. Do not open the compressor unit
piping to the atmosphere for more than 15 minutes. The compressors contain POE oil that is
very hygroscopic; it quickly absorbs water from the atmosphere. The longer the compressor
piping is open to the atmosphere, the harder it will be to fully evacuate. If left open too long, the
POE oil may need to be replaced before achieving the required vacuum level.
POE oils also have a property that makes them act as a solvent in a refrigeration system.
Maintaining system cleanliness is extremely important because the oil will tend to bring any
foreign matter back to the compressor. Refer to the ASHRAE refrigeration handbook for
general good-practice refrigeration piping.
Outdoor Ambient °F
(°C)
Condenser Model
50/60Hz
Condenser
Qty
Receiver
Part #
Receiver
Qty
Head Pressure
Kit
Head Pressure Kit
Qty
-30 to 100 (-34 to 38)
DCSL415
2
185010G2
1
/G4
2
2
179711G1
2
-30 to 105 (-34 to 41)
DCSL616
2
179713G1
1
/G2
2
1
179711G2
2
35 to 105 (2 to 41)
DCSL616
2
181610G2
1
/G4
2
2
179711G1
2
1. 120V heater
2. 230V heater
Table 6.6 Receivers and head pressure kits for Liebert Lee-Temp condensers
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
125
Содержание Liebert XD Series
Страница 1: ...Liebert Xtreme Density System Design Manual...
Страница 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Страница 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Страница 45: ...Figure 3 22 Liebert XD return header orientation Vertiv Liebert Xtreme Density System Design Manual 45...
Страница 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Страница 76: ...Figure 4 12 Liebert XDO internal mounting location Vertiv Liebert Xtreme Density System Design Manual 76...
Страница 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Страница 90: ...Figure 4 23 Suspending single Liebert XDV from Unistruts Vertiv Liebert Xtreme Density System Design Manual 90...
Страница 103: ...Figure 5 4 Piping locations floor stand and valve assembly Vertiv Liebert Xtreme Density System Design Manual 103...
Страница 112: ...Figure 5 16 Front view of Liebert XDP and electrical enclosure Vertiv Liebert Xtreme Density System Design Manual 112...
Страница 115: ...Figure 5 19 Liebert XDP high voltage connections 60Hz Vertiv Liebert Xtreme Density System Design Manual 115...
Страница 116: ...Figure 5 20 Liebert XDP high voltage connections 50Hz Vertiv Liebert Xtreme Density System Design Manual 116...
Страница 120: ...Figure 6 2 Condenser planning dimensional data Six fan units Vertiv Liebert Xtreme Density System Design Manual 120...
Страница 121: ...Figure 6 3 Typical condenser footprint dimensions Vertiv Liebert Xtreme Density System Design Manual 121...
Страница 138: ...Figure 6 13 Drycooler planning dimensional data Eight fan units Vertiv Liebert Xtreme Density System Design Manual 138...
Страница 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Страница 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Страница 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Страница 170: ...Figure 7 11 CAN Isolator location within the Liebert XDP XDC Vertiv Liebert Xtreme Density System Design Manual 170...
Страница 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Страница 198: ...Figure 9 7 Liebert XDP model number nomenclature Vertiv Liebert Xtreme Density System Design Manual 198...
Страница 199: ......