Data Description
Definitions
Supply Refrigerant
Temperature
Supply refrigerant temperature.
Supply Refrigerant
Under Temp
(Supply Refrigerant Temperature) has dropped below a specified threshold.
System Condensation
Detected
System condensation detected.
System Control Mode
System Control Mode
System Date and Time
The system date and time
System Event
Acknowledge/Reset
Reset and/or acknowledge all events.
System On/Off Control
Turn system functionality On or Off.
System Operating State
Current operating state of the system.
System Status
The operating status for the system
Table 8.1 Liebert XDC/XDP monitoring points (continued)
Data Description
Definitions
Cold Aisle Over Temp
Threshold
Upper threshold value used in the (Cold Aisle Temp Out of Range) event.
Cold Aisle Over Temp
Threshold
Upper threshold value used in the (Cold Aisle Temp Out of Range) event.
Cold Aisle Temp Out of
Range
The air temperature in the cold aisle is either above (Cold Aisle Over Temp Threshold) or below (Cold Aisle Under Temp
Threshold).
Cold Aisle Under Temp
Threshold
Lower threshold value used in the (Cold Aisle Temp Out of Range) event.
Cold Aisle Under Temp
Threshold
Lower threshold value used in the (Cold Aisle Temp Out of Range) event.
Communication Status
Communication status of remote device.
Cooling Capacity
Cooling capacity in use, expressed as a percentage of the maximum rated capacity.
Cooling Capacity
Cooling capacity in use, expressed in kilowatts.
Ext Fan Issue
One or more fans are not operating within their operational parameters.
Ext Fan Issue - Event
Control
Enable/disable the activation of the (Ext Fan Issue) event. If set to “disabled,” the event will not be annunciated. This
implies that the event will not be placed in any active event list or in any event history list.
Ext Fan Issue - Event
Type
The event type for the (Ext Fan Issue) event.
Ext Remote Shutdown
Unit is shut down by a remote signal.
Ext Remote Shutdown -
Event Control
Enable/disable the activation of the (Remote Shutdown) event. If set to 'disabled', the event will not be annunciated. This
implies that the event will not be placed in any active event list or in any event history list.
Ext Remote Shutdown -
Event Type
The event type for the (Remote Shutdown) event.
Ext System Condensation
Detected
External system condensation detected.
Ext System Condensation
Detected - Event Control
Enable/disable the activation of the (Ext System Condensation Detected) event. If set to “disabled,” the event will not be
annunciated. This implies that the event will not be placed in any active event list or in any event history list.
Ext System Condensation
Detected - Event Type
The event type for the (Ext System Condensation Detected) event.
Table 8.2 Liebert XD Smart Module monitoring points
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
179
Содержание Liebert XD Series
Страница 1: ...Liebert Xtreme Density System Design Manual...
Страница 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Страница 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Страница 45: ...Figure 3 22 Liebert XD return header orientation Vertiv Liebert Xtreme Density System Design Manual 45...
Страница 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Страница 76: ...Figure 4 12 Liebert XDO internal mounting location Vertiv Liebert Xtreme Density System Design Manual 76...
Страница 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Страница 90: ...Figure 4 23 Suspending single Liebert XDV from Unistruts Vertiv Liebert Xtreme Density System Design Manual 90...
Страница 103: ...Figure 5 4 Piping locations floor stand and valve assembly Vertiv Liebert Xtreme Density System Design Manual 103...
Страница 112: ...Figure 5 16 Front view of Liebert XDP and electrical enclosure Vertiv Liebert Xtreme Density System Design Manual 112...
Страница 115: ...Figure 5 19 Liebert XDP high voltage connections 60Hz Vertiv Liebert Xtreme Density System Design Manual 115...
Страница 116: ...Figure 5 20 Liebert XDP high voltage connections 50Hz Vertiv Liebert Xtreme Density System Design Manual 116...
Страница 120: ...Figure 6 2 Condenser planning dimensional data Six fan units Vertiv Liebert Xtreme Density System Design Manual 120...
Страница 121: ...Figure 6 3 Typical condenser footprint dimensions Vertiv Liebert Xtreme Density System Design Manual 121...
Страница 138: ...Figure 6 13 Drycooler planning dimensional data Eight fan units Vertiv Liebert Xtreme Density System Design Manual 138...
Страница 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Страница 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Страница 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Страница 170: ...Figure 7 11 CAN Isolator location within the Liebert XDP XDC Vertiv Liebert Xtreme Density System Design Manual 170...
Страница 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Страница 198: ...Figure 9 7 Liebert XDP model number nomenclature Vertiv Liebert Xtreme Density System Design Manual 198...
Страница 199: ......