3.25 Electrical
Make all wiring and electrical connections in accordance with local and national codes. Refer to the
applicable table in
Specifications and Model Number Nomenclature
on page 183 regarding wire size and
circuit protection requirements. Refer to electrical schematic when making connections.
3.26 Temperature/Humidity Sensor Locations
The display panel sensor and Liebert iCOM sensor (shipped loose) must always be installed in the
conditioned space. The display panel sensor and Liebert iCOM sensor may be mounted on the Liebert
XDC/XDP’s front door if the unit is located in the area that it conditions.
The remote temperature / humidity sensor for the Liebert XDP and the Liebert XDC should be installed in
the higher-temperature portion of the cold aisle where the Liebert XD modules are located. Alternatively,
it can be placed on the return air side of the primary air mover, such as a Liebert DS, in the room if it
represents the conditions where all the Liebert XD cooling modules are located. It should not be installed
where ambient air might cause false readings, for example, near unsealed doors, windows and similar
areas.
3.27 Connecting Liebert XDP and Liebert XD Cooling Modules in a CANbus
Network
A Controller Area Network (CAN) is a specialized internal communication network. It allows the Liebert
XDP and the Liebert XD smart modules to communicate without a host computer. Networking a Liebert
XDP with smart modules enables the smart modules to be controlled and monitored from the Liebert XDP.
The Liebert XD smart modules CANbus is to be networked only to the Liebert XDP that is supplying
coolant to the smart modules.
Figure 3.30 Liebert XD system with CANbus
3.27.1 CANbus Cables
The Liebert XDP may be connected to smart modules with CANbus cables. The shielded cable consists of
three pairs of twisted wires with a six-pin RJ-12 connector.
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
60
Содержание Liebert XD Series
Страница 1: ...Liebert Xtreme Density System Design Manual...
Страница 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Страница 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Страница 45: ...Figure 3 22 Liebert XD return header orientation Vertiv Liebert Xtreme Density System Design Manual 45...
Страница 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Страница 76: ...Figure 4 12 Liebert XDO internal mounting location Vertiv Liebert Xtreme Density System Design Manual 76...
Страница 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Страница 90: ...Figure 4 23 Suspending single Liebert XDV from Unistruts Vertiv Liebert Xtreme Density System Design Manual 90...
Страница 103: ...Figure 5 4 Piping locations floor stand and valve assembly Vertiv Liebert Xtreme Density System Design Manual 103...
Страница 112: ...Figure 5 16 Front view of Liebert XDP and electrical enclosure Vertiv Liebert Xtreme Density System Design Manual 112...
Страница 115: ...Figure 5 19 Liebert XDP high voltage connections 60Hz Vertiv Liebert Xtreme Density System Design Manual 115...
Страница 116: ...Figure 5 20 Liebert XDP high voltage connections 50Hz Vertiv Liebert Xtreme Density System Design Manual 116...
Страница 120: ...Figure 6 2 Condenser planning dimensional data Six fan units Vertiv Liebert Xtreme Density System Design Manual 120...
Страница 121: ...Figure 6 3 Typical condenser footprint dimensions Vertiv Liebert Xtreme Density System Design Manual 121...
Страница 138: ...Figure 6 13 Drycooler planning dimensional data Eight fan units Vertiv Liebert Xtreme Density System Design Manual 138...
Страница 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Страница 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Страница 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Страница 170: ...Figure 7 11 CAN Isolator location within the Liebert XDP XDC Vertiv Liebert Xtreme Density System Design Manual 170...
Страница 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Страница 198: ...Figure 9 7 Liebert XDP model number nomenclature Vertiv Liebert Xtreme Density System Design Manual 198...
Страница 199: ......