72 Chapter 10 Service And Maintenance
APM 300 Integrated UPS Single Module And Parallel System User Manual
Air filters
Fixing bar
Fixing bar
Air filters
Fixing bar
Air filter
Air filter
Fixing bar
Figure 10-1
Replacing air filters (switch cabinet)
10.4
Maintenance Of UPS And Options
UPS and the options need common maintenance:
1. Keep good history record. Keeping good history record facilitates failure treatment.
2. Keep clean, so as to prevent UPS from the invasion of dust and moisture.
3. Maintain appropriate ambient temperature. The most appropriate temperature for battery is 20
°
C to 25
°
C.
Too low temperature will reduce the battery capacity and too high temperature will reduce the battery life.
4. Check the wiring. Check the tightening of all connected screws, and there should be routine tightening at
least once a year.
5. Check regularly if there is any abnormity in the superior or subordinate switch to ensure cutting off the
import or export when the current is too large. Maintenance staff should be familiar with the typical ambient
conditions where UPS is working in order to rapidly position which ambient conditions are unusual; the setting
of UPS operation control panel should be known as well.
For information of the UPS battery maintenance, refer to
6.5 Battery Maintenance
.
10.3
Replacement Procedures Of Air Filter
The UPS provides four air filters on the back of the front doors of the main power cabinet and switch cabinet
respectively. Each air filter is fixed by a fixing bar on either side. The replacement procedures of each air filter
are the same. The following takes the switch cabinet as an example to describe the air filter (see Figure 10-1)
replacement procedures.
1. Open the front door of the switch cabinet to reveal the air filters on the back of the front door.
2. Remove the fixing bar on either side of the air filter that needs replacement.
3. Remove the air filter, and insert a clean one.
4. Replace the fixing bar.