16 Chapter 2 Mechanical Installation
APM 300 Integrated UPS Single Module And Parallel System User Manual
1. Use the DIP switch on the front panel of the module to set the module address. The setting range is from 1
to 10. The module address should be exclusive. The setting method is shown in Table 2-1.
Table 2-1 DIP switch setting method
DIP switch setting
Module address
1
2
3
4
5
6
7
8
9
10
2. Place the ready switch on the front panel of the module to the up position (that is, in unready state).
3. Remove the dummy plate in the installation position of the module, insert the module in the installation
position, and push it into the cabinet.
4. Secure the module to the main power cabinet through the fixing holes on both sides of the front panel of
the module.
5. Place the ready switch to the down position (that is, in ready state).