Chapter 3 Electrical Installation 17
APM 300 Integrated UPS Single Module And Parallel System User Manual
Chapter 3
Electrical Installation
This chapter introduces the electrical installation of the UPS, including the procedures or methods for power
cabling and control cabling, the distance from floor to connection point, and the connection of cabinets.
The UPS requires both power cabling and control cabling once it has been mechanically installed. All control
cables, whether shielded or not, should be run separately from the power cables.
Warning: professional installation
1. Do not power on the UPS before the arrival of authorized service engineer.
2. The UPS cables must be routed by an authorized engineer in accordance with the information contained in this
chapter.
3.1
Power Cables
3.1.1
System Configuration
The cable size of the system power cable shall meet the following requirements:
UPS input cables
The size of the UPS input cable differs with the UPS power ratings and input AC voltages, provided that it
meets the requirement of rated input current, including the rated battery charge current, see Table 3-1.
UPS bypass and output cables
The size of the UPS bypass and output cable differs with the UPS power rating and output AC voltages,
provided that it meets the requirement of rated output or bypass current, see Table 3-1.
Battery cables
Each UPS connects to its battery through two cables connecting to the positive pole and negative pole. The
cable size of the battery cable differs with the UPS power ratings, provided that it meets the battery discharge
current requirement when the battery discharges to near EOD voltage, see Table 3-1.
3.1.2
Maximum Steady State AC And DC Currents
Table 3-1
Maximum steady state AC and DC currents
UPS rated
power (kVA)
Rated current (A)
Input mains current
1
,
2
with full battery recharge
Total output current
2
at full load (36 cells)
Battery discharge
current at EOD
380V
400V
415V
380V
400V
415V
300
560
530
510
450
430
410
1050
270
514
477
459
405
387
369
945
240
448
424
408
360
344
328
840
210
392
371
357
315
301
287
735
180
336
318
306
270
258
246
630
150
280
265
255
225
215
205
525
120
224
212
204
180
172
164
420
90
168
159
153
135
129
123
315
60
112
106
102
90
86
82
210
30
56
53
51
45
43
41
105
Содержание Liebert APM 300
Страница 1: ......
Страница 2: ......
Страница 7: ...The Manual Covers The Following Equipment Product Model APM 300 Liebert APM 300...
Страница 9: ......