16 Chapter 2 Mechanical Installation
Liebert EXM 80kVA ~ 200kVA UPS User Manual
battery adopts rack mounting or is mounted far from the UPS with other installation mode, the battery
circuit breaker shall be installed near the battery, and the cabling distance shall be minimized.
2.6.3
Storage
Should the UPS not be installed immediately, it must be stored with the original packaging in a room for
protection against excessive humidity and heat sources (see Table 11-2). The battery needs to be stored
in a dry and cool place with good ventilation. The most suitable storage temperature ranges from 20°C to
25°C.
Warning
During battery storage, periodically charge the battery according to the battery manufacturer instructions. In the
charge process, temporarily connect the UPS to the mains and activate the battery by recharging the battery.
2.7
Mechanical Requirement
2.7.1
Composition
As a cabinet of 600mm width, the 80kVA ~ 120kVA system provides the options such as rectifier input
switch, bypass input switch, and output switch.
As a cabinet of 600mm width, the 160kVA ~ 200kVA system also provides the optional switch cabinet
(width: 400mm) which contains the rectifier input switch, bypass input switch, output switch and
maintenance switch.
2.7.2
Moving Cabinet
Warning
1. The lifting equipment for moving the UPS cabinet must have enough lift capacity.
2. The UPS has installed castors. When removing the UPS from the shipping pallet, pay attention to keeping the
UPS from sliding. Ensure that adequate personnel and lifting equipment are available when removing the shipping
pallet.
3. Due to its intensity, the castor may not be valid on the uneven surface.
4. The center of gravity of the UPS cabinet is high; avoid falling over during the cabinet movement.
5. Vertical hanging of cabinet is not allowed.
Ensure that the weight of the UPS does not exceed the capacity of the lifting equipment. For the UPS
weight, refer to Table 11-3.
The UPS cabinet can be moved by forklift or other similar lifting equipment.
For short distance movement, the castors can be used.
2.7.3
Clearance
Because the UPS has no grille at the two sides, there is no special clearance requirement on the two sides.
Besides the local regulations, to enable routine tightening of the power terminals within the UPS, it is
recommended that clearance around the front of the UPS should be sufficient to enable free passage of
personnel with the door fully open. Meanwhile, maintain at the back of the cabinet a clearance at least
500mm to permit adequate circulation of air coming out of the UPS.