Chapter 8 Options 111
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Parallel cabinet mechanical connection
The power cabinet and optional switch cabinet need to be connected at installation site, see Figure 8-2.
B (D)
A (C)
Main power cabinet
Optional switch cabinet
After parallel installation, remove the handle and extension
bar at bottom of the main power cabinet, then use the
dummy plate (accessory) to cover the hole.
Bolt M10*25 (1 piece)
Plain washer M10 (1 piece)
Spring washer M10 (1 piece)
Bolt M10*25 (1 piece)
Plain washer M10 (1 piece)
Spring washer M10 (1 piece)
A (C) Amplified view
Installation position 1
Installation position 2
Extension bar
Remove the soket head cap screw,
and pull the extension bar.
Figure 8-2 Mechanical cabinet connection
Note
After parallel installation, remove the handle and extension bar at bottom of the main power cabinet, then use the
dummy plate (accessory) to cover the hole. Note that the label of Q3 should be removed becausee the Q3 is not
used any more. Then ensure that the switch is in OFF state, see the image below: