Chapter 6 Battery 87
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Warning: hazardous battery voltage present behind covers
3. Observe the following safety precautions when working on the batteries:
a) The battery shall be firmly and reliably connected. After the connection is completed, the screw connections
between all the terminals and the batteries shall be calibrated. The requirements on torque specified in the
specifications or user manual provided by the battery manufacturer shall be satisfied. The connections between all
the wiring terminals and the batteries shall be inspected and tightened at least once a year. Otherwise it may cause
fire!
b) The battery appearance must be inspected before accepting and using the battery. If there exists any package
damage, dirty battery terminal, terminal erosion, rust, or enclosure crack, deformation or liquid leakage, replace it
with a new battery. Otherwise, battery capacity reduction, electric leakage or fire may be caused.
Battery damaged during handling or transportation
After a week of normal charge/discharge experiment
c) The battery is very heavy. Please use proper method to move and lift the battery, so as to prevent any damage
to human being or the battery terminal. Severe damage to the battery may cause fire.
d) The battery connecting terminal shall not be subject to any force, such as the pulling force or twisting force of
the cable, otherwise, the internal connection of the battery may be damaged. Severe damage to the battery may
cause fire.
e) The battery shall be installed and stored in a clean, cool and dry environment. Do not install the battery in a
sealed battery chamber or a sealed room. The battery room ventilation shall at least meet the requirement of
EN50272-2001. Otherwise, battery bulging, fire or even human injury may be caused.
f) The battery shall be installed far away from the heating products (e.g. transformer), used or stored far away from
any fire source, and shall not be burnt or put into fire for heating. Otherwise, battery leakage, bulging, fire or
explosion may be caused.
g) Do not directly connect any conductor between the positive and negative terminals of the battery. Remove the
finger rings, watch, necklace, bracelet and other meta items before operating the battery, and ensure that the tools
(e.g., wrench) are covered with insulating material. Otherwise, battery burning, human death/injury or explosion may
be caused.
h) Do not disassemble, modify or demolish the battery. Otherwise, battery short circuit, liquid leakage or even
human injury may be caused.