Chapter 3 Electrical Installation 31
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Pin
Name
Meanings
Pin
Name
Meanings
17
GND_DRY
External maintenance
isolation switch status
(24V/10mA rated); Pin17
/Pin19 open for QOP
closed
18
CHG SHUT
Charger shutdown
(24V/10mA rated).
Pin18/Pin20 shorted
for charger off
command
19
QOP STATUS
20
GND_DRY
21
QBP STATUS
External maintenance
switch status
(24V/10mA rated);
Pin21/Pin23 shorted for
QBP closed
22
QE STATUS
External output switch
status (24V/10mA
rated); Pin22/Pin24
open for QE closed
23
GND_DRY
24
GND_DRY
25
NC
Reserved
26
NC
Reserved
27
UT1 485+
RS485 channel #1, 485+
28
UT2 485+
RS485 channel
#2,485+
29
UT1 485-
RS485 channel #1, 485-
30
UT2 485-
RS485 channel #2,
485-
31
GND_MON
Reserved
32
NC
Reserved
Note
For dry contact port J26, Pin28, Pin30 and Pin27, Pin29 must adopt the metal wire shielded twisted-pair cable, and
the end connecting to the UPS must be well connected to the enclosure.
3.2.5
Programmable Dry Contact Ports J23 ~ J25
The dry contact ports J23 ~ J25 are shown in Figure 3-10 and described in Table 3-6 and Table 3-7. The
dry contact voltages are 24Vdc/250Vac, and the current is 5A. 1, 3, 5 is a group of dry contacts, and 2, 4, 6
are another group of dry contatcs. These six-goup of dry contacts are programmable via the Paramset,
and you can select any one from the output signals 1~9 in Table 3-6.
1
3
5
J23
1
3
5
1
3
5
J24
J25
2
4
6
2
4
6
2
4
6
Figure 3-10 Dry contact ports J23 ~ J25
Table 3-6
Selectable dry contact ports
Port
Pin
Meanings
1. Bypass
back-feed
Normally open
contact
Bypass back-feed normally open contact. Closed when there is
bypass back-feed
Common contact
Bypass back-feed common contact
Normally
closed
contact
Bypass back-feed normally closed contact. Open when there is
bypass back-feed
2. Inverter state
Normally open
contact
Inverter state normally open contact. Closed when the inverter is on
Common contact
Inverter state common contact