9SX 8000
9SX 11000
9PX 8000
9PX 11000
9SX EBM 240V
9PX EBM 240V

Installation  
and user manual

Copyright © 2012 

EATON

 

All rights reserved.

Service and support:

Call your local service representative

8-11kVA EU_EN

Содержание 9PX EBM 240V

Страница 1: ...9SX 8000 9SX 11000 9PX 8000 9PX 11000 9SX EBM 240V 9PX EBM 240V Installation and user manual Copyright 2012 EATON All rights reserved Service and support Call your local service representative 8 11kV...

Страница 2: ...Page 2 8 11kVA EU_EN...

Страница 3: ...Certification standards Safety IEC EN 62040 1 Ed 1 2008 p UL 1778 4th edition EMC IEC EN 62040 2 Ed 2 2006 p FCC part 15 Class A Performance IEC EN 62040 3 Ed 2 0 2011 p IEC 61000 4 2 ESD level 3 p IE...

Страница 4: ...h the National Electric Code ANSI NFPA 70 US installations only The upstream circuit breaker must be easily accessible The unit can be disconnected from AC power source by opening this circuit breaker...

Страница 5: ...sources connection 24 4 3 Separate input source connection 25 4 4 Frequency converter connection 25 5 Operation 26 5 1 UPS startup and shutdown 26 5 2 Operating modes 27 5 3 Transferring the UPS betw...

Страница 6: ...se comprises over 50 of recycled cardboard p Sacks and bags are made of polyethylene p Packing materials are recyclable and bear the appropriate identification symbol p 01 PET Materials Abbreviations...

Страница 7: ...f your equipment Providing outstanding performance and reliability the Eaton 9SX and 9PX s unique benefits include True online double conversion technology with high power density utility frequency in...

Страница 8: ...kg Dimensions inch mm D x W x H 9SX 8000 Power Module 42 19 27 6 x 17 3 x 5 1 700 x 440 x 130 9SX 11000 Power Module 46 21 27 6 x 17 3 x 5 1 700 x 440 x 130 9PX 8000 Power Module 42 19 27 6 x 17 3 x...

Страница 9: ...ion port 4 Connector for ROO Remote On Off control 5 Connectors for automatic recognition of battery module 6 Connector for Parallel operation for 9PX only 7 Connector for RPO Remote Power Off control...

Страница 10: ...1Ki 8 2 6 4 3 5 1 7 1 Input Output terminal blocks 2 Input Output cables for connection to the UPS 3 Bypass terminal blocks for connection to the UPS 4 Normal AC source switch 5 Bypass AC source switc...

Страница 11: ...BM 50 5 0kW 5 5kVA Efficiency 95 Escape Up Down Enter On Off button Battery mode indicator orange Bypass mode indicator orange The following table shows the indicator status and description Indicator...

Страница 12: ...operating normally The UPS is powering and protecting the equipment Battery mode 1 beep every 10 seconds A utility failure has occured and the UPS is on Battery mode The UPS is powering the equipment...

Страница 13: ...ults stored Reset fault list Clears faults Identification Product type model Part Serial number UPS NMC firmware Com card IPv4 Com card IPv6 Com card MAC Detected accessories Register product Links to...

Страница 14: ...after 5 min of back up time if load is less than threshold Disabled Sleep mode Enabled Disabled If Disabled LCD and communication will turn OFF immediately after UPS is OFF If Enabled LCD and communi...

Страница 15: ...king the cabinet Unpacking the cabinet in a low temperature environment may cause condensation to occur z in and on the cabinet Do not install the cabinet until the inside and outside of the cabinet a...

Страница 16: ...nstructions 9 Software CD ROM If you ordered an optional Extended Battery Module EBM verify that the following additional items are included z with the EBM 3 4 2 1 1 Battery power cable attached with...

Страница 17: ...nd firmly 1 Plug the EBM power cable s into the battery connector s Up to 12 EBMs may be connected to the UPS 2 Verify that the EBM connections are tight and that adequate bend radius and strain relie...

Страница 18: ...the LCD panel p If you ordered other UPS accessories refer to specific user manuals to check the tower installation with the UPS To install the cabinet 1 Place the UPS on a flat stable surface in its...

Страница 19: ...move the center cover of the front panel 2 Remove the four screws to open the front panel 3 Remove the three screws to pull out the metal protection cover of the battery 4 Pull out the plastic handle...

Страница 20: ...20 8 11kVA EU_EN Rack mounting of UPS EBM and accessory modules p Follow steps 1 to 4 for module mounting on the rails 1 1 3 4 4 3 2 The rails and necessary hardware are supplied by EATON 3 Installat...

Страница 21: ...ker 8000VA D curve 50A 11000VA D curve 63A 2 poles circuit breaker G N L2 L1 N L2 L1 to UPS Normal AC source 2 Recommended cable cross sections Terminal position Wire function Terminal wire size ratin...

Страница 22: ...d 8 10 11 z UPS with separate Normal and Bypass AC inputs 8 10 11 Bypass AC Normal AC Load Main low voltage switchboard MLVS Isolation transformer Change in SEA between upstream and downstream or galv...

Страница 23: ...and downstream or galvanic isolation required 8 10 11 Bypass AC Normal AC Load MLVS1 MLVS2 Isolation transformer z Frequency converter without Bypass AC input Configuration used when the frequency of...

Страница 24: ...es Normal AC source and Bypass AC source are open O Off Always connect the ground wire first If you ordered a HotSwap MBP refer to the specific user manual to check the terminal blocks connection of t...

Страница 25: ...o the Bypass AC source terminal blocks 6 Insert the Output cable through the cable gland 7 Connect the three cables to the Output terminal blocks 8 Put back and secure the terminal blocks cover with t...

Страница 26: ...larms and restart if necessary 7 Verify that the indicator illuminates solid indicating that the UPS is operating normally and powering the output The UPS should be in Online mode The EBM charge to 90...

Страница 27: ...mode In the event of a UPS overload or internal failure the UPS transfers your equipment to utility power Battery mode is not available and your equipment is not protected however the utility power c...

Страница 28: ...ing on output mode If Disabled the UPS output is shutdown Interrupt time This setting is displayed to define the break duration during transfer to Bypass only if transfer out of tolerance is enabled 1...

Страница 29: ...ugh the display 1 Press any button to activate the menu options then select Event log 2 Scroll through the listed events 5 8 Retrieving the Fault log To retrieve the Fault log through the display 1 Pr...

Страница 30: ...tected Pin 3 not low battery Pin 4 not on Battery Pin 5 user common Pin 6 on Bypass Pin 7 low battery Pin 8 load protected Pin 9 on Battery n o contact normally open n c contact normally closed The re...

Страница 31: ...age SELV circuit This circuit must be separated from any hazardous voltage circuits by reinforced insulation The RPO must not be connected to any utility connected circuits Reinforced insulation to th...

Страница 32: ...avoid accidental load loss z Connectivity Cards Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of devices The 9SX and 9PX models have...

Страница 33: ...wer Software suite Each 9SX and 9PX UPS ships with Eaton Intelligent Power Software suite To begin installing see the instructions accompanying the Software suite CD Eaton Software suite provides up t...

Страница 34: ...untimes Replace batteries at least every 4 years to keep units running at peak efficiency 7 2 Storing the equipment If you store the equipment for a long period recharge the battery every 6 months by...

Страница 35: ...lacing batteries replace with the same type and number of batteries or battery packs z Contact your service representative to order new batteries Proper disposal of batteries is required Refer to your...

Страница 36: ...Plug the EBM cable s into the battery connector s Up to twelve EBMs may be connected to the UPS 4 Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for ea...

Страница 37: ...UPS 4 Select Control then Go to Bypass 5 Turn the HotSwap MBP switch to the Normal position the red LED on the HotSwap MBP goes Off indicating that the load is now powered by the UPS Bypass LED shoul...

Страница 38: ...utility failure has occurred and the UPS is in Battery mode The UPS is powering the equipment with battery power Prepare your equipment for shutdown Battery low The UPS is in Battery mode and the bat...

Страница 39: ...n to normal operation when the temperature drops 5 C below the warning level If the condition persists shut down the UPS Clear vents and remove any heat sources Allow the UPS to cool Ensure the airflo...

Страница 40: ...Model number z Serial number z Firmware version number z Date of failure or problem z Symptoms of failure or problem z Customer return address and contact information z If repair is required you will...

Страница 41: ...M 700 x 440 x 130 27 6 x 17 3 x 5 1 46 21 9PX11KiPM 700 x 440 x 130 27 6 x 17 3 x 5 1 46 21 Model EBM Dimensions D x W x H mm inch Weight lb kg 9SXEBM240 680 x 440 x 130 26 8 x 17 3 x 5 1 128 58 9PXEB...

Страница 42: ...rm 125 150 UPS shuts down after 1 minute 150 UPS shuts down after 1s Voltage waveform Sinewave Harmonic distortion 2 THDV on linear load 5 THDV on non linear load Transfer time Online mode 0 ms no bre...

Страница 43: ...r configuration 9SXEBM240 240Vdc 20 x 12V 7Ah 9PXEBM240 240Vdc 20 x 12V 9Ah Fuses 63A for 8kVA models 80A for 11kVA models and EBM Type Sealed maintenance free valve regulated lead acid with minimum 3...

Страница 44: ...ttery power Load Devices or equipment connected to the UPS output HE mode Operating mode by which the load is supplied directly by the AC source if it is within the tolerances defined by the user This...