Vertiv™ NetSure™ IPE Series Rectifier Installation and User Manual
19
Figure 20:
Unscrew the Cable Gland Caps
Figure 21:
Cable Gland Diagram
7.
Slide the prepared cable(s) into the rectifier case through the appropriate cable gland. Connect the appropriate cables into
the appropriate pins of the customer connection terminal blocks. Tighten the terminal block’s screws to secure the wire.
Torque as shown in
for a “Customer Wiring Location Diagram”. Refer to the following for specific
wire instructions.
-
External Alarm and Control Connections: See “External Alarm and Control Connections” on page 21.
-
AC Input and AC Input Equipment Grounding Connections: See “Nominal 120 VAC / 208 VAC / 220 VAC / 230 VAC /
240 VAC Input and AC Input Equipment Grounding Connections” on page 22.
-
Output Connections: See “-48 VDC Output Connections” on page 22.
-
Battery Connections: See “Battery Connections” on page 23.
NOTE!
If multiple sealing cable adapters are furnished, select and install the appropriate sealing cable adapter.
Cable Gland
P/N 63204183
Cable Gland
P/N 63204186
Cable Gland
P/N 63204185
Cable
Gland
Nut
Flat Seal
Cable Gland
Sealing
Cable Adapter
Sealing
Pin
Cable Gland Cap