Vertiv™ NetSure™ IPE Series Rectifier Installation and User Manual
3
WARNING!
The module is rated for continuous operation at full output power up to +50 °C (+122 °F). Operation between
+50 °C (+122 °F) and +75 °C (+167 °F) will result in output power decrease. Operation above +75 °C (+167 °F) is considered
abnormal and should be used on a temporary
1
basis only.
1
Temporary Operation at Abnormal Temperature: Temporary operation is defined as a period of not more than eight
consecutive hours per day, and a total of not more than 15 days in a year. (This refers to a total of 120 hours in any
given year, but no more than 15 occurrences in that one-year period.)
Other power rating values are as follows (refer to
):
a)
At an ambient temperature of +65 °C (+149 °F), the power delivered by the rectifier is 800 W.
b)
At an ambient temperature of +75 °C (+167 °F), the power delivered by the rectifier is 0 W.
Figure 3:
Power Derating Based on Temperature
6.
Regulation:
a)
Static: Steady state regulation is ±0.6% as controlled within the rectifier for any and all combinations of load from 5% to
100% load, input voltage, and input frequency at a constant ambient temperature.
b)
Dynamic: Response time ≤200 us and overshoot ≤5% for load changes at 50% - 25% - 50%
and 50% - 75% - 50% at rated output current.
For any step load change within the range of 10% to 90% of full load within 50 microseconds, per Telcordia
GR-947-CORE, the maximum voltage transient will not exceed 5% of the initial steady state voltage within 50±10
microseconds. Recovery to within 1% of the initial steady state voltage does not exceed 4 milliseconds.
7.
Filtering:
a)
Voice Band Noise: Peak-peak voltage is ≤200 mV at 0 MHZ to 20 MHZ and normal output voltage.
b)
Wide Band Noise: Wideband noise voltage is ≤50 mV at 3.4 kHz to 150 kHz and ≤20 mV at 0.15 MHz to 30 MHz.
1.4.2
AC Input Ratings
1.
Voltage: Nominal 120 VAC / 208 VAC / 220 VAC / 230 VAC / 240 VAC, single phase, 3-wire, 50 Hz / 60 Hz, with an operating
range of 85 VAC to 300 VAC. Acceptable input frequency range is 45 Hz to 65 Hz.
Permitted Variation: 85 VAC to 300 VAC.