Vertiv™ NetSure™ IPE Series Rectifier Installation and User Manual
5
Table 4:
Typical Input Data with 60 Hz Input
Nominal
Input Voltage
Percent
of Full Load
Input Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat Dissipation
BTU/Hr
120
0
0.533
64.1
18.7
0.283
0
63.602
25
4.403
528.6
524.8
0.994
90.028
178.566
50
8.438
1006.9
1005.8
0.999
92.735
249.324
75
12.66
1503
1501.9
0.999
92.945
361.533
100
--
--
--
--
--
--
110
--
--
--
--
--
--
208
0
0.896
187.4
13.4
0.070
0.000
45.586
25
2.615
545.9
517
0.947
90.968
159.338
50
4.840
1010.4
991.9
0.982
94.052
201.306
75
7.150
1487.7
1475.7
0.992
94.648
269.487
100
9.506
1974.8
1961.7
0.994
94.720
353.405
110
10.460
2171.1
2159.6
0.995
94.679
392.108
240
0
1.031
248.9
13.0
0.050
0.000
44.494
25
2.376
575.8
517.3
0.907
91.333
152.975
50
4.241
1020.7
989.2
0.969
94.309
192.093
75
6.198
1489.7
1471.3
0.987
94.931
254.473
100
8.203
1969.9
1955.1
0.993
95.040
330.885
110
9.018
2163.5
2152.1
0.995
95.009
366.517
Note:
System output is initially adjusted to 54 volts DC as measured at the system sense point at 50% of full load
and nominal input. “Percent of Full Load” refers to percent of 34.48 amperes.
Table 5:
Maximum Input Current with 60 Hz Input
Nominal Input
Voltage
Input
Voltage
Input Current
(Amperes)
208/240
176
11.98
Note:
At 100% of full load with output adjusted to 58 volts DC as
measured at the output terminals.
Figure 4:
Efficiency Curve (@ 230 VAC, 50 Hz)