Vertiv™ NetSure™ IPE Series Rectifier Installation and User Manual
22
•
Maximum Switching Current: 2 A.
•
Maximum Carrying Current: 2 A.
3.5.3
Rectifier Fail Alarm
A rectifier fail alarm activates if any of the following conditions occur. Contacts close between terminals J1-1 and J1-2 on the alarm
connector during a rectifier fail alarm condition.
•
Severe load sharing imbalance.
•
Rectifier output disabled for any reason, including overvoltage shutdown and internal output fuse open.
3.5.4
AC Fail Alarm
An AC fail alarm activates if AC input voltage is lost.
Contacts close between terminals J2-1 and J2-2 on the alarm connector during an AC fail alarm condition.
3.5.5
Fuse Alarm
A fuse alarm activates if any of the internal fuses open.
Contacts close between terminals J7-1 and J7-2 on the alarm connector during a fuse alarm condition.
3.5.6
CAN
Terminal CAN+ on the Alarm Connector: CAN_H (associated with J4-1).
Terminal CAN- on the Alarm Connector: CAN_L (associated with J4-2).
3.6
Nominal 120 VAC / 208 VAC / 220 VAC / 230 VAC / 240 VAC Input and
AC Input Equipment Grounding Connections
The rectifier is equipped with AC input terminal blocks (located on the connector board inside the rectifier). Mating connectors are
provided. Customer must provide wiring to the mating connector. See
. See also
“Customer Wiring to Terminal Blocks Located Inside Rectifier Case” starting on page 16.
•
Recommended AC input wire size is 12 AWG.
•
This rectifier requires an external AC input branch circuit protective device rated for 25 A.
3.7
-48 VDC Output Connections
WARNING!
Check for correct polarity before making connections.
The rectifier is equipped with DC output terminal blocks (located on the connector board inside the rectifier). Mating connectors are
provided. Customer must provide wiring to the mating connector. See
. See also
“Customer Wiring to Terminal Blocks Located Inside Rectifier Case” starting on page 16.