Vertiv™ NetSure™ IPE Series Rectifier Installation and User Manual
7
5.
Surge Protection: EN61000-4-5 up to level 4, Telcordia GR-1089-Core, IEEE C62.41-2002, YD/T 731-2002.
Performance Criteria B.
AC Power Terminals
Test Level
Source
Impedance
Performance
Criteria
Line to Line
Line to Ground
± 4 kV
± 4 kV
2 ohms
B
NA
± 6 kV
12 ohms
B
DC Power Terminals:
Test Level
Source
Impedance
Performance
Criteria
Line to Line
Line to Ground
± 500 V
± 500 V
2 ohms
B
± 800 V
± 800 V
2 ohms
B
The test method is described in EN 61000-4-5. In this test the DC-cables shall
be 5 m long.
6.
Single Rectifier Audible Noise: At 25 °C ≤45 dB(A). Measurement made at 0.6 m distance in front of rectifier and at same
horizontal line of the middle of rectifier.
7.
High Voltage Category (per UL60950): III
8.
Power Distribution System: TN/TT/IT
9.
EMI/RFI Suppression:
a)
The rectifier conforms to the requirements of FCC rules Part 15, Class B for radiated and conducted emissions limits.
b)
The rectifier conforms to the requirements of European Norm, EN55022, Class B for radiated and conducted emissions
limits.
10.
Pollution Degree: Degree 3.
1.4.4
Compliance
Information
1.
EMC: ETSI EN 300 386, FCC CFR 47 Part 15 class B, Telcordia GR-1089-CORE.
2.
EMI Load Range: 10% to 100%.
3.
Safety: UL 60950-1, UL 60950-22, EN 60950-1, IEC 60950-1.
4.
NEBS.
1.4.5
Standard Features
1.
Type of Power Conversion Circuit: High frequency.
2.
Input Protection:
a)
Input Over/Under Voltage Protection: The rectifier will shut down at low or high voltage input; based on the following
voltage levels:
Low Voltage Disable Point: 80 VAC, ±5 V; hysteresis is at least 15 VAC for restart.