Vertiv™ NetSure™ IPE Series Rectifier Installation and User Manual
23
3.8
Battery Connections
WARNING!
Check for correct polarity before making connections.
The rectifier is equipped with battery terminal blocks (located on the connector board inside the rectifier). Mating connectors are
provided. Customer must provide wiring to the mating connector and battery as required. See
. Torque as indicted in
. See also “Customer Wiring to Terminal Blocks Located Inside Rectifier Case” starting on page 16.
•
Wire size is determined by site requirements.
Figure 25:
Customer Wiring Location Diagram
3.9
Paralleling Rectifiers for Redundancy
DO NOT EXCEED THE LOAD RATING OF A SINGLE RECTIFIER.
To parallel rectifiers, connect the CAN bus of each rectifier together. Connect CAN_H to CAN_H and CAN_L to CAN_L.
Cable Gland Information
Designation
Vertiv P/N
Alarm
63204186
DC Output 1
63204183
DC Output 2
63204183
DC Output 3
63204185
Battery
63204185
AC Input
63204183
Designation
Cable Selection
Alarm
UL2464 22 AWG*8C
DC Output 1 SJOOW 300V 10 AWG 2/C
DC Output 2 SJOOW 300V 10 AWG 2/C
DC Output 3 SJOOW 600V 6 AWG 2/C
Battery
SJOOW 600V 6 AWG 2/C
AC Input
SJOOW 300V 12 AWG 3/C