Chapter 1 Overview 5
SmartCabinet Series Solution Product for IDC or Computer Rooms User Manual
System type
Component
Main function
Feature
SmartCabinet
integrated unit)
Interface parts of air
duct
An interface between the air
duct and cabinet
Easy to install and easy to disassemble, and the air
duct can be easily installed and connected with the
system
Air duct
(customer shall
prepare by himself)
Installing air duct
According to the application site, the customer can
choose a reasonable length and location for the
installation of air duct.
1.6 Ambient Requirements
Operation Environment
The SmartCabinet product should be installed in the place that is far away from the heating source or sparks, and
shall avoid direct sunshine and there shall be no erosive gases and organic solvent in the room. The operating
conditions are shown in Table 1-3.
Table 1-3 Operating condition
Item
Requirement
Model
600/800mm wide standard unit
600mm wide integrated unit
MSC-XXS65XBXXXXX/
MSC-XXS85XBXXXXX
Installation position
Make sure that the installtion field is level,
Space height is not less than 2400mm.
Max. equivalent horizontal distance between the
indoor unit and the outdoor unit of the AC: 30m,
Vertical distance
Δ
H: -5m
≤
Δ
H
≤ 15m
Make sure that the installtion field is level,
Space height is not less than 2300mm.
Installation field
In computer room or office area. The distance
from the front / rear door to the wall or other
obstacles is larger than 1.0m
The clearance among the room, office area,
front and rear doors, the wall or obstacles
should be greater than 1.0m
The clearance between the side door and the
wall or obstacles should be greater than 45cm
Good draught condition must be needed in the
installation field for this type .
Environmental
requirements
Indoor*: 0°C ~ 40°C
Outdoor unit of air conditioner: standard model, -
15°C ~ +45°C
0
℃~
40
℃
Ambient humidity
*1
30%RH ~ 95%RH
Altitude
*2
Derating is required when the altitude is above 1000m
Operation voltage range
P+N+PE
,
220Vac/230Vac/240Vac
Note*1
when the whole unit is operating in high temperature and high humidity environment, condensing
water may appear on the external surface of front glass door and the display panel, Normal
phenomena, does not affect the using.
Note*2
For the air conditioner, derating is required when the altitude is above 1000m .For the UPS, when
derating is required
,
please refer to
Liebert
®
ITA2 5kVA
~
20kVA UPS User Manual and Liebert
®
ITA 3kVA UPS User Manual
Storage Environment
The storage environment requirements are listed in Table 1-4.
Table 1-4 Storage environment requirements
Item
Requirement
Storage environment
Indoor, clean without dust
Ambient humiduty
5%RH ~ 95%RH (Non-condensing)
Ambient temperature
-15°C ~ + 50°C