18 Chapter 3 Installation
SmartCabinet Series Solution Product for IDC or Computer Rooms User Manual
Figure 3-7 Outdoor unit installation
3) Installed against wall for outdoor unit, and the distance from air return side to wall shall be 0.2 m. See following
Figure 3-8.If there are multiple outdoor units that need to be placed with one above the other, follow the method
shown in Figure 3-8 to install them.
B r a c k e t
4 m
0 . 5 m
5 0 m m
5 0 m m
M i n . 5 0 m m
O u t d o o r u n i t b a s e
B a s e
A i r f l o w
A i r f l o w
O u t -
d o o r
u n i t
O u t -
d o o r
u n i t
N o t e :
1 . U s e 5 # a n g l e i r o n f o r b r a c k e t , w h e n
t w o u n i t s a r e i n s t a l l e d w i t h o n e a b o v e
t h e o t h e r .
2 . U s e 6 . 5 # c h a n n e l s t e e l f o r b r a c k e t , w h e n
t h r e e u n i t s a r e i n s t a l l e d w i t h o n e a b o v e t h e
o t h e r .
0.2m
Figure 3-8 Installing multiple outdoor units with one above the other
2. Installing the outdoor unit on top of the cabinet
There is a special method for installing outdoor unit higher than indoor unit, that is, installing the outdoor unit on top of
the cabinet. The detailed installing procedures are as follows:
1) Life or carry the outdoor unit removed from the cabinet onto top of the cabinet. See Figure 3-9 for the installing
direction of AC outdoor unit.
2) Adjust the placing position of the AC to align the AC foot stands with the corresponding screw holes on top of the
cabinet, and then place metal press pieces on the foot stands, at last, use four screws to fix the AC outdoor unit on
the top plate of the cabinet, as shown in Figure 3-9.