80
Chapter 6 Web Page Of MSC intelligent monitoring unit
SmartCabinet Series Solution Product for IDC or Computer Rooms User Manual
Figure 6-65 Access management
In the event of adding visitor, in the textbox of
IP Address of RDU Manager
, type the new IP address of the RDU
manager, and click the
Add Visitor
button to finish the configuration.
Note
1. Up to three RDU manager IP addresses can be added in the system.
2. In the event of adding visitor, if you select to use an agent, you also need to configure the agent server.
3. SNMP Configuration
Click the
Network Setting
submenu under the
System Options
menu, and then click the
SNMP Configuration
tab,
you can configure SNMP agent. The MSC intelligent monitoring system supports V2 and V3 versions of SNMP agent.
As shown in Figure 6-66, the specific setting method of SNMP V2 is as follows:
1) Set NMS IP (host IP address of SNMP agent data receiving end);
2) Set Trap Level:
‘Enable’ or ‘disable’;
3) Keep defaults for other items.
Figure 6-66 SNMP V2 setting
As shown in Figure 6-67, the specific setting method of SNMP V3 is as follows:
1) Set NMS IP (host IP address of SNMP agent data receiving end);
2) Set the Trap Level:
‘Enable’ or ‘disable’;
3) Set the Name;
4) Set the User Type:
‘Authenticated & Encrypted’, ‘Authenticated & Not Encrypted’, ‘Not Authenticated & Not
Encrypted
’;
5) Select Authentication Protocol:
‘MD5’, ‘SHA’;
6) Select Privacy Protocol:
‘DES’;
7) Self-define Authentication Password and Privacy Password.