92 Chapter 7 Maintenance
SmartCabinet Series Solution Product for IDC or Computer Rooms User Manual
Figure 7-4 Select AC on homepage
b) Open Control page(Figure 7-5)
Figure 7-5 Open Control page
c) Set the
“manual run allowed” to "Yes"and ensure the compressor is “on” (Figure 7-6)
Figure 7-6 manual run allowed
d) S
et the “Compressor Capacity Output Value” and “Fan Speed” to 43% and 81%(Figure 7-7).
Figure 7-7 Set compressor output and fan speed
e)
After the output of the compressor and fan is stable at the set value (about 10 minutes), read the “exhaust pressure
measurement value” on the “Sampling” page (Figure 7-8), and perform the data in Table 7-2 for comparison, ensure
that the pressure value error does not exceed 0.5 Bar.