Chapter 7 Maintenance 87
SmartCabinet Series Solution Product for IDC or Computer Rooms User Manual
Chapter 7 Maintenance
This chapter expounds the maintenance of SmartCabinet, including safety instructions, maintenance of the main
components, disassembly and troubleshooting.
7.1 Safety Instructions
Warning
1. Switch off the power input during the equipment maintenance. Switch off the equipment power unless the testing device needs
power.
2. Only authorized professional technicians are allowed to maintain the system.
1. All maintenance and operation must follow the local laws, especially the regulations about the electric power,
refrigeration and production.
2. Comply with the manufacturer instructions during maintenance. Failure to observe this could result in invalidation
of warranty.
3. Ignoring the safety instructions will endanger personnel safety and environment.
4. Unsuitable components will lead to performance decrease or equipment shutdown, it is commended to use the
components made by Vertiv.
7.2 Maintenance Of The Main Components
Note
Regular maintenance & inspection are necessary to ensure proper operation of the equipment.
MSC intelligent monitoring unit Maintenance
Restoring default setting
Restoring default setting can be finished through two modes: software or hardware.
For software restoring, refer to Restore System in
6.4.7 System Options
.
Hardware restoring includes restoring MSC intelligent monitoring unit admin password (default username: admin,
password: Vertiv) and MSC intelligent monitoring unit IP address (default IP address: 192.168.0.252). You can short
pin2 and pin3 of jumper J18 on the MSC intelligent monitoring unit card to complete hardware restoring. The jumper
position is shown in Figure 3-22.
FAQ
Q1
: How to deal with that there is no access to MSC intelligent monitoring unit login page when the MSC intelligent
monitoring unit communication is normal?
A
: There are three measures to solve the problem:
Step 1: Ensure that the IP address is correct;
1. Please ensure that the network cable is connected to the correct port.
2. The default IP address of MSC intelligent monitoring unit: 192.168.0.252.
Step 2: Ensure the connectivity of IP address.
To ensure the connectivity of IP address, you can use PING/ping command, and the method is as follows:
1) Click the
icon at the lower left corner, and type
‘cmd’ in the
extbox, as shown in Figure 7-1.