20306745
25
VWDV70 Series Gas Fireplace
FIREPLACE INSTALLATION
NOTE:
The gas line connection may be made using 1/2"
rigid tubing or an approved
fl
ex connector. Since some
municipalities have additional local codes it is always best
to consult your local authorities and the current edition of
the National Fuel Gas Code ANSI.Z223.1, NFPA54. In
Canada CSA-B149 (1 or 2) Installation Code.
A listed manual shutoff valve must be installed upstream of
the appliance. Union tee and plugged 1/8" NPT pressure
tapping point should be installed upstream of the appliance.
Figure 36
IMPORTANT:
Install main gas valve (equipment shutoff
valve) in an accessible location. The main gas valve is for
turning on or shutting off the gas to the
fi
replace.
Check your building codes for any special requirements for
locating equipment shutoff valve to
fi
replaces.
Apply pipe joint sealant lightly to male threads. This will
prevent excess sealant from going into pipe. Excess seal-
ant in pipe could result in clogged burner system valves.
W
ARNING
Only persons licensed to work with gas piping
may make the necessary gas connections
to this appliance.
CAUTION
A manual shutoff valve must be installed
upstream of the appliance. Union tee
and plugged 1/8" NPT pressure tapping
point should be installed upstream of the
appliance. Figure 36
CAUTION
Use pipe joint sealant that is resistant to
liquid petroleum (LP) gas.
Natural Gas
From Gas Meter
(4.5" w.c. to 10.5" w.c. Pressure)
Propane/LP
From External Regulator
(11" w.c. to 13" w.c. Pressure)
Figure 36 -
Gas Connection
3" Minimum
Cap
Approved Flexible
Gas Line
CSA Design-Certi
fi
ed
Equipment Shutoff Valve
with 1/8" NPT Tap*
Sediment Trap/Drip Leg
Tee Joint
Pipe Nipple
We recommend that you install a sediment trap/drip leg in
supply line as shown in
Figure 36
. Locate sediment trap/
drip leg where it is within reach for cleaning. Install in piping
system between fuel supply and burner system. Locate
sediment trap/drip leg where trapped matter is not likely
to freeze. A sediment trap collects moisture and contami-
nants and keeps them from going into the burner system
gas controls. If sediment trap/drip leg is not installed or is
installed wrong, burner system may not run properly.