VWDV70 Series Gas Fireplace
VENTING INSTALLATION
VERTICAL SIDEWALL INSTALLATION
Step 1
Locate vent opening on the wall. It may be necessary to
fi
rst position the
fi
replace and measure to obtain hole lo-
cation. Depending on whether the wall is combustible or
noncombustible, cut opening to size.
Figure 15
(For com-
bustible walls
fi
rst frame in opening.)
Combustible Walls:
Cut a 10
1
⁄
2
"H x 10
1
⁄
2
"W (267 x 267
mm) hole through the exterior wall and frame as shown.
Figure 15
Noncombustible Walls:
Hole opening must be 8
1
⁄
2
" (216
mm) in diameter.
Vent Opening for Combustible Walls
10
1
⁄
2
"
(267 mm)
Min.
Fireplace Hearth
Framing Detail
Opening for Noncombustible Wall
8
1
⁄
2
"
(216 mm)
Fireplace Hearth
FP2293
Figure 15 -
Locate vent opening on wall
10
1
⁄
2
"
(267 mm) Min.
Step 2
Secure
fi
restop to the inside frame, center in the 10
1
⁄
2
" x
10
1
⁄
2
" vent opening.
Step 3
Place
fi
replace into position. Measure the vertical height
(X) required from the base of the
fl
ue collars to the center
of the wall opening.
Figure 16
Step 4
Using appropriate length of pipe section(s) attach to
fi
re-
place with three (3) screws. Follow with the installation of
the elbow.
Step 5
Measure the horizontal length requirement
fi
guring a 1
1
⁄
4
"
(32 mm) overlap, i.e. from the elbow to the outside wall
cap.
Figure 17
X
Figure 16 -
Vertical Height Requirement
FP1181
Figure 17 -
Horizontal Length Requirement
X
FP1182
Step 6
Use appropriate length of pipe sections — telescopic or
fi
xed — and install.
Sealing vent pipe and fi restop gaps with high tem-
perature sealant will restrict cold air being drawn in
around fi replace.
Step 7
Guide the vent terminations 5" and 8" collard into their
respective vent pipes. Double check that the vent pipes
overlap the collars by a minimum 1
1
⁄
4
" (32 mm). Secure
the termination to the wall with screws provided and caulk
around the wall plate to weatherproof. As an alternative to
screwing the termination directly to the wall, you may also
use expanding plugs or an approved exterior construction
adhesive.
Always install horizontal venting on a level
plane.
Support horizontal pipes every 36" (914 mm)
with metal pipe straps.