VWDV70 Series Gas Fireplace

NOTE REGARDING VENTED PRODUCTS

This product must be installed by a licensed plumber or gas 

fi

 tter 

when installed within the Commonwealth of Massachusetts.
Any residence with a direct vent product must have a carbon 
monoxide (CO) detector installed in the residence.
Installation of the 

fi

 replace or vented gas log in the State of 

Massachusetts requires the damper to be permanently removed 
or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a 
bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have a 
T shutoff valve. 

NOTE REGARDING VENT FREE PRODUCTS

This product must be installed by a licensed plumber or gas 

fi

 tter 

when installed within the Commonwealth of Massachusetts.
In addition, vent free products may not be installed in a 
bedroom or bathroom regardless of size or type in the State of 
Massachusetts.
Flex line installation must not exceed 36 inches and must have a 
T shutoff valve.

CARBON MONOXIDE DETECTOR REQUIREMENTS

(2) Revise 10.8.3 by adding the following additional requirements:
(a)  For all side wall horizontally vented gas fueled equipment 
installed in every dwelling, building or structure used in whole or in 
part for residential purposes, including those owned or operated 
by the Commonwealth and where the side wall exhaust vent 
termination is less than seven (7) feet above 

fi

 nished grade in the 

area of the venting, including but not limited to decks and porches, 
the following requirements shall be satis

fi

 ed:

1. 

Installation of carbon monoxide detectors. 

At the time 

of installation of the side wall horizontal vented gas fueled 
equipment, the installing plumber or gas 

fi

 tter shall observe that 

a hard wired carbon monoxide detector with an alarm and battery 
back-up is installed on the 

fl

 oor level where the gas equipment is 

to be installed. In addition, the installing plumber or gas 

fi

 tter shall 

observe that a battery operated or hard wired carbon monoxide 
detector with an alarm is installed on each additional level of the 
dwelling, building or structure served by the side wall horizontal 
vented gas fueled equipment. It shall be the responsibility of 
the property owner to secure the services of quali

fi

 ed licensed 

professionals for the installation of hard wired carbon monoxide 
detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the hard 
wired carbon monoxide detector with alarm and battery back-up 
may be installed on the next adjacent 

fl

 oor level.

 

b.  In the event that the requirements of this subdivision 

can not be met at the time of completion of installation, the owner 
shall have a period of thirty (30) days to comply with the above 
requirements; provided, however, that during said thirty (30) day 
period, a battery operated carbon monoxide detector with an 
alarm shall be installed.

MASSACHUSETTS RESIDENTS ONLY

2. 

Approved Carbon Monoxide Detectors. 

Each carbon 

monoxide detector as required in accordance with the above 
provisions shall comply with NFPA 720 and be ANSI/UL 2034 
listed and IAS certi

fi

 ed.

3. 

Signage.

 A metal or plastic identi

fi

 cation plate shall be 

permanently mounted to the exterior of the building at a minimum 
height of eight (8) feet above grade directly in line with the 
exhaust vent terminal for the horizontally vented gas fueled 
heating appliance or equipment. The sign shall read, in print size 
no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

4. 

Inspection.

 The state or local gas inspector of the side 

wall horizontally vented gas fueled equipment shall not approve 
the installation unless, upon inspection, the inspector observes 
carbon monoxide detectors and signage installed in accordance 
with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) 

Exemptions:

 The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled "Equipment Not 

Required To Be Vented" in the most current edition of NFPA 54 as 
adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled 

equipment installed in a room or structure separate from the 
dwelling, building or structure used in whole or in part for 
residential purposes.
(c)  

Manufacturer requirements — Gas Equipment Venting 

System Provided. 

When the manufacturer of Product Approved 

side wall horizontally vented gas equipment provides a 
venting system design or venting system components with the 
equipment, the instructions provided by the manufacturer for 
installation of the equipment and the venting system shall include:

1. Detailed instructions for the installation of the venting system 

design or the venting system components; and

2. A complete parts list for the venting system design or venting 

system.
(d) 

Manufacturer requirements — Gas Equipment Venting 

System Not Provided. 

When the manufacturer of a Product 

Approved side wall horizontally vented gas fueled equipment 
does not provide the parts for venting the 

fl

 ue gases, but 

identi

fi

 es “special venting systems,” the following requirements 

shall be satis

fi

 ed by the manufacturer:

1. The referenced "special venting system" instructions shall be 

included with the appliance or equipment installation instructions; 
and

2. The “special venting systems” shall be Product Approved 

by the Board, and the instructions for that system shall include a 
parts list and detailed installation instructions.
(e)  A copy of all installation instructions for all Product Approved 
side wall horizontally vented gas fueled equipment, all venting 
instructions, all parts lists for venting instructions, and/or all 
venting design

Please read and follow these special requirements

Содержание VWDV70NTSCSB

Страница 1: ...rom a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service...

Страница 2: ...ll Installation 27 Signature Command System Wiring Diagram 28 Thank you and congratulations on your purchase of a Vermont Castings Group Fireplace PLEASE READ THE INSTALLATION AND OPERATION INSTRUCTIO...

Страница 3: ...installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the f...

Страница 4: ...ype appliances draw all combustion air from outside of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GA...

Страница 5: ...t Stone Set Wall Switch Kit ITEMS REQUIRED FOR INSTALLATION Phillips Screwdriver Framing Materials Hammer Wall Finishing Materials Saw and or saber saw Level Measuring Tape Pliers Electric Drill and B...

Страница 6: ...2 6M 1848 mm 81 6 2067 mm 6 6QE 167 mm 2356 587 mm 17 6 440 mm 1 6M 45 mm 6 6QE 167 mm 4856M 1226 mm 31 6 803 mm 17 6M 451 mm 4856O 1232 mm 1456O 368 mm 9156 2315 mm Rough Opening Width 23 6 594 mm 23...

Страница 7: ...se Installation Y 4 Minimum Figure 4 Possible Fireplace Locations NOTE Refer to cold climate pilot information on Page 38 for more information on standing pilot vs intermittent pilot options These uni...

Страница 8: ...pet tile or other combustible material other than wood flooring If installed on carpet or vinyl flooring the appliance shall be installed on a metal wood or noncombustible material panel extending ful...

Страница 9: ...eel or other materials with a UL fire rating of Zero may be used to cover up the black face up to the fireplace glass door opening It is permissible to bring combustible wall board to the top of the s...

Страница 10: ...dding This will ensure proper adhesion of both the tape and mud The supplied board is very porous 50 6QE 1284 mm 656M 159 mm 235 6QE 608 mm 92 2337 mm Wall Board 3 6 98 mm 7 6M 197 mm 656M 159 mm 10 2...

Страница 11: ...al framing Use the 8 x 3 4 self tapping screws provided Metal Framing Maintain 161 2 419 mm to Combustible Framing FP2941 Figure 10 If a mantel will be installed and the attachment points fall upon th...

Страница 12: ...ions VENTING INSTALLATION Read all instructions completely and thoroughly before attempting installation Failure to do so could result in serious injury property damage or loss of life Operation of im...

Страница 13: ...be considered a combustible material Maintain proper clearances to all combustible materials Treatment of firestops and construction of the chase may vary from building type to building type These ins...

Страница 14: ...91cm for appliances 100 000 BTU h 30kW 6 15cm for appliances 10 000 BTU h 3kW 9 23cm for appliances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances 50 000 BTU h 15kW C Clearance to perm...

Страница 15: ...the fireplace Vertical Dimension from the Base of Unit to the Center of the Horizontal Vent Pipe Dimensions in Feet 84 2134 mm From Floor to Center NOTE Termination in an alcove space spaces open onl...

Страница 16: ...lars to the center of the wall opening Figure 16 Step 4 Using appropriate length of pipe section s attach to fire place with three 3 screws Follow with the installation of the elbow Step 5 Measure the...

Страница 17: ...finished outside wall The maximum number of 90 elbows per side wall installation is three 3 Figure 18 A minimum of 36 914 mm is required before a 90 elbow Figure 19 Figure 18 Maximum Three 3 90 Elbows...

Страница 18: ...ole through the wall 2 Remove soil to a depth of approximately 16 406 mm below base of snorkel Install drain pipe Install window well not supplied Refill hole with 12 305 mm of coarse gravel leaving a...

Страница 19: ...914 mm Min Figure 25 Maximum Elbow Usage FP1179 Up to two 45 elbows may be used within the horizontal run For each 45 elbow used on the horizontal plane the maximum horizontal length must be reduced...

Страница 20: ...when passing through ceilings walls roofs enclosures attic rafters etc Do not pack air spaces with insulation Also note maximum vertical rise of the venting system and any maximum horizontal offset l...

Страница 21: ...stible material 4 Connect a section of pipe and extend up through the hole NOTE If an offset is needed to avoid obstructions you must support the vent pipe every three 3 feet Use wall straps for this...

Страница 22: ...extend the inner flexible vent 4 Slide the inner vent onto the adapter collar for a minimum 13 4 overlap 5 Locate the clamp at approximately 3 4 from the flex end and tighten 6 Secure the clamped inne...

Страница 23: ...installation instruc tions and Figure 32 E Installing flexible venting to horizontal termination assemblies FLEX VENT INSTALLATION Figure 32 Typical Vertical Flex Vent Installation Figure 33 Typical...

Страница 24: ...r sleet WARNING A qualified installer or service person must connect appliance to gas supply Follow all local codes CAUTION For propane LP units never connect fireplace directly to the propane LP supp...

Страница 25: ...ner system valves WARNING Onlypersonslicensedtoworkwithgaspiping may make the necessary gas connections to this appliance CAUTION A manual shutoff valve must be installed upstream of the appliance Uni...

Страница 26: ...ith this appliance Install and attach 1 2 gas line onto shut off valve 3 After completing gas line connection purge air from gas line and test all gas joints from the gas meter to the fireplace for le...

Страница 27: ...tacle into an electrical circuit Wire with mini mum 60 C wire in accordance with prevailing codes 2 Remove the external junction box cover by removing the screw from the side of the outside firebox wa...

Страница 28: ...ox Plug In Connector Control Box to Solenoid DC Power green Valve Ground Gas In Gas Out 15 ft Cable A C MODULE PLUG IN CONNECTOR WHITE BLACK BLACK WHITE GREEN WHITE BLACK Opt Blower Opt Aux Light 300...

Страница 29: ...ove front light socket cover 2 Use a Phillips screwdriver to remove socket plate with bulb to be replaced Figure 41 3 Replace socket and socket cover in reverse order PORCELAIN PANELS NOTE You must pu...

Страница 30: ...n flames Place three 3 pieces of hearth glass lenses supplied into opening on hearth in front of burner Unpack all decorative colored glass and stones included in kit Carefully mix the two colors of d...

Страница 31: ...ket Mounting Screws Installation Instructions NOTE The two 2 large rear logs should be installed be fore installing the decorative colored glass on hearth 1 Remove the glass door Use glass door latch...

Страница 32: ...the left end of the rear left log 1 by aligning the recess with the key protrusion on the rear left log Figure 52 Medium Top Right Log 5 Figure 53 8 Place the medium top right log 5 onto the center o...

Страница 33: ...the burner port area Small Front Right Log 7 Figure 56 shows the completed log set installation 11 It is not necessary but if you choose you may place a few stones randomly around the front of the log...

Страница 34: ...n place NOTICE It is the responsibility of the installer to ensure the barrier is affixed to the fireplace at the time of instal lation CERTIFIED SAFETY BARRIER NOTE A barrier designed to reduce the r...

Страница 35: ...bor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will...

Страница 36: ...n Page 31 If you do not smell gas go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker wil...

Страница 37: ...ERY INSTALLATION The Command Center uses four 4 AA batteries as back up for power outages The system can operate for approximately six 6 months on battery power To Install Batteries not included 1 Pre...

Страница 38: ...in Use paper clip to depress button One beep for RF receiver ON or two beeps for RF receiver OFF will be given as confirmation Refer to Figure 57 for location 2 After the RF receiver is on holding the...

Страница 39: ...ing the Fireplace Off There are three ways to turn the fireplace off 1 Flip the master switch to the off O position This will turn the entire system OFF 2 Press the OFF button to Medium Low then Off 3...

Страница 40: ...e away from your house for an extended period of time Never leave anything on top of the surface of the transmitter Information Bar Touch Area Logo Bar Menus Adjustment Controls Function Areas of the...

Страница 41: ...n and the green LED on the Command Center will flash for 10 seconds 4 During the 10 seconds press the OFF button on the transmitter to learn Another two beeps will be given to confirm suc cess Figure...

Страница 42: ...Or TOUCH SCREEN REMOTE CONTROL OPERATION b Use the OFF down buttons to decrease the Set Time to zero Or c Slide down on the arrow buttons to exit TIMER mode and shut off the fireplace Thermostat Mode...

Страница 43: ...Delay and Off Delay in the next section TOUCH SCREEN REMOTE CONTROL OPERATION 4 After the signal is sent the ON up and OFF down but tons become flame height controller again 5 When the fan button is...

Страница 44: ...s TIMER but ton and THERMO button at the same time for 3 sec onds The backlight will flash once to indicate that the setting has changed to B 2 When the current setting is B pressing TIMER button and...

Страница 45: ...is blank Low Battery Check battery installation or replace batteries LCD display shows funny display Low Battery Reset the transmitter see Reset ting the Transmitter setting Appliance does not come on...

Страница 46: ...the fireplace The parts to convert from LP to natural gas must be purchased from an authorized dealer Refer to Page 54 Conversion parts included Burner orifice refer to Table 1 Pilot orifice Gas valv...

Страница 47: ...ith injectors provided in kit Refer to Table 1 for correct injector sizes Injectors are differ ent in size and specific to each burner 13 For conversion to LP Unscrew three 3 air shutters through lens...

Страница 48: ...he burner porting pilot air opening and burner air opening are free of obstructions at all times PILOT FLAME The flames from the pilot should be visually checked as soon as the heater is installed and...

Страница 49: ...oor properly secured Never operate the fireplace if the glass is broken Replace any glass that is chipped cracked or broken Replacement glass door assemblies MUST be supplied by the fireplace manufact...

Страница 50: ...upply Go through Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using...

Страница 51: ...twire Junction Box w Cover 2 20303352 7 Wire Nut 10 20302355 8 Safety Barrier 1 20306595K Accessories Field Installed 9 Porcelain Panel Kit Black complete 1 VWDV70PB 9a Porcelain Panel Black Rear Left...

Страница 52: ...VWDV70 Series Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM ENGINE 2 3 4 5 6 7 8 5 5 5 8 8 9 10 11a 12 13 14 9 9 10 10 11c 11b 15 16 17 18 19 20 15 15 18 19 21 22 23 24 25 33 21 21 26 27 2...

Страница 53: ...13 Valve 1 80D0001 14 Flexline 18 w Shutoff Valve 1 69D0030 15 Grommet 4 73D0189 16 Fitting 3 8 NPT x 3 8 Brass Male 1 025660 17 Tube Valve to T 1 20302884K 18 Tube Straight 2 20302885K 19 Brass Tee 3...

Страница 54: ...Black 6 20303041K 2 Stone M Sand 6 20303042K 3 Stone M White 6 20303043K 4 Stone M Dark Gray 6 20303044K 5 Stone White 4 78D0136K 6 Stone Sand 4 78D0140K 7 Stone Dark Gray 4 78D0138K 8 Stone Brown 4 7...

Страница 55: ...20306745 55 VWDV70 Series Gas Fireplace HOT 1 2 3 4 5 6 9 7 8 10 VENTING COMPONENTS VENT COMPONENTS FOR 5 X 8 PIPE...

Страница 56: ...3 4 9 Pipe Length 58DVA 09 1207 5DT 09 3 4 12 Pipe Length 58DVA 12 1206 5DT 12 5D12 3 4 24 Pipe Length 58DVA 24 1204 5DT 24 5D24 3 4 36 Pipe Length 58DVA 36 1203 5DT 36 5D36 3 4 48 Pipe Length 58DVA...

Страница 57: ...to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed MASSACHUSETTS RESIDENTS ONLY 2...

Страница 58: ...anty will be void if the appliance is not installed by a qualified installer in accordance with the installation instructions The Limited Lifetime Warranty will also be void if the appliance is not op...

Страница 59: ...4 1 09 Efficiency Ratings Model EnerGuide Ratings DOE Fireplace Efficiency AFUE VWDV70NTSC 79 3 71 4 VWDV70PTSC 79 8 77 5 After conversion to LP 149 Cleveland Drive Paris Kentucky 40361 www vermontcas...

Отзывы: