VDH Products BV
Document 063319 - version 3.12
Page:
59 of 78
Number
Description
Range
Value
Default
5000
Analog Input Settings
5001
5002
5003
5004
5005
Input rel. humidity sensor
Input gas concentration sensor
Input pressure sensor 1
Input CO2 sensor
Input pressure sensor 2
0..7
0..7
0..7
0..7
0..7
-
-
-
-
-
1
2
3
0
0
6000
Analog Output Settings
6001
6002
6003
6004
6005
6006
6007
6008
6100
6101
6200
Output 1
0 = 0 Volt
1 = setpoint temperature
2 = average all control sensors
3 = P(I) cooling zone 1
4 = P(I) cooling zone 2
5 = P(I) cooling zone 3
6 = P(I) heating zone 1
7 = P(I) heating zone 2
8 = P(I) heating zone 3
9 = 0 Volt
10 = 0 Volt
11 = 0 Volt
12 = combined pressure and temperature based
PID fan control
13 = alternative pressure fan control, PI
control direction according Figure 5
14 = alternative pressure fan control, PI
control direction according Figure 6
Output 2
Output 3
Output 4
Reserved, do not change!
Reserved, do not change!
Reserved, do not change!
Reserved, do not change!
0 V out at temperature
10 V out at temperature
I/O board selection
0 = new model (with TLC5628 DA convertor)
1 = old model (with MAX529CPP DA convertor)
0..14
0..14
0..14
0..14
-
-
-
-
-99.9..150
-99.9..150
0..1
-
-
-
-
-
-
-
-
°C
°C
-
0
0
0
0
-
-
-
-
0.0
100.0
0
7000
Function test
7001
7002
7003
7004
7005
7006
7007
7008
7009
7010
Relay 1 forced on
Relay 2 forced on
Relay 3 forced on
Relay 4 forced on
Relay 5 forced on
Relay 6 forced on
Relay 7 forced on
Relay 8 forced on
Relay 9 forced on
Relay 10 forced on
0..1
0..1
0..1
0..1
0..1
0..1
0..1
0..1
0..1
0..1
-
-
-
-
-
-
-
-
-
-
0
0
0
0
0
0
0
0
0
0
Содержание PROBA
Страница 73: ...VDH Products BV Document 063319 version 3 12 Page 73 of 78...
Страница 74: ...VDH Products BV Document 063319 version 3 12 Page 74 of 78 Appendix M Technical Specification PROBA110...
Страница 75: ...VDH Products BV Document 063319 version 3 12 Page 75 of 78...
Страница 76: ...VDH Products BV Document 063319 version 3 12 Page 76 of 78...
Страница 77: ...VDH Products BV Document 063319 version 3 12 Page 77 of 78 Jumper settings...