VDH Products BV
Document 063319 - version 3.12
Page:
27 of 78
Non Fatal Errors can be recognized by the letter 'F' in the display, followed
by a number code. The meaning of the number is:
F x
Temperature sensor x at fault. The regulation continues by
using the operational temperature sensors.
F 10
Relative humidity sensor at fault.
F 11
Gas concentration sensor at fault.
F 12
Pressure sensor 1 at fault.
F 13
CO2 sensor at fault /Pressure sensor 2 at fault.
F 2x
Temperature sensor x is higher than the relative maximum 1.
F 3x
Temperature sensor x is lower than the relative minimum 1.
F 4x
Temperature sensor x is higher than the relative maximum 2.
F 5x
Temperature sensor x is lower than the relative minimum 2.
F 101
Maximum gas time exceeded during gassing based on gas
concentration.
F 102
Gas is empty
F 150
Minimum rel. humidity alarm
F 151
Maximum rel. humidity alarm
F 200
No communication when used in network
F 210
Fans are > 15 minutes blocked, while program is running
F 250
Minimum pressure alarm
F 251
Maximum pressure alarm
F 300
Interrupt of power supply
F 400
Non Fatal alarm input active
During a Non Fatal Error the NON FATAL ALARM relay will be activated.
In Appendix F (Error messages, see page 62) all possible fatal and non fatal
errors are listed.
Depending on the internal settings (see chapter '4.2.4'; page 34) the alarms
will be active if the
PROBA110
is on, or only during the execution of a
program or STANDBY regulation.
Finally determine if the ALARM-relay can be reset by pressing the
ALARM-
RESET
key or not. In the last case the ALARM relay will return to the normal
position if the failure is removed.
Содержание PROBA
Страница 73: ...VDH Products BV Document 063319 version 3 12 Page 73 of 78...
Страница 74: ...VDH Products BV Document 063319 version 3 12 Page 74 of 78 Appendix M Technical Specification PROBA110...
Страница 75: ...VDH Products BV Document 063319 version 3 12 Page 75 of 78...
Страница 76: ...VDH Products BV Document 063319 version 3 12 Page 76 of 78...
Страница 77: ...VDH Products BV Document 063319 version 3 12 Page 77 of 78 Jumper settings...