Series 613
INSTALLATION
984360EC
Edition 12.08.2022
57/149
5.12.7.6
Interface RS232/RS485
Sub Group
Parameter
ID [hex]
Data Type Acc
NV
Unit Min
Max Description
Operation Mode
A1010000
SINT8
RW
NV
0
2
0:RS232
1:RS485
2:Service Interface Over RS232
Settings
Baud Rate
A1110100
SINT8
RW
NV
0
7
0:1200
1:2400
2:4800
3:9600
4:19200
5:38400
6:57600
7:115200
Data Bit Length
A1110200
SINT8
RW
NV
0
1
0:7
1:8
Stop Bit
A1110300
SINT8
RW
NV
0
1
0:1
1:2
Parity Bit
A1110400
SINT8
RW
NV
0
2
0:None
1:Even
2:Odd
Topology
A1110800
SINT8
RW
NV
0
1
Only used if Operation Mode = RS485
0:Full Duplex
1:Half Duplex
Network
A1110900
SINT8
RW
NV
0
1
Only used if Operation Mode = RS485
0:Multiple Devices
1:Point to Point
Address
A1110A00
UINT8
RW
NV
0
255 Only used if Operation Mode = RS485
Command Set
A1110500
SINT8
RW
NV
0
2
0:IC
1:PM
2:PM V2
3: Tylan
4: Tylan Type 1
5: Tylan Type 2
Command Termination
A1110B00
SINT8
RW
NV
0
2
0: Carriage Line
Feed
1: Line Feed
2: Carriage Return
R A Answer
Only for Command Set = IC,PM, PMV2
0: Standard
1: i:76
Second Answer
Only for Command Set = PM, PMV2
0:Off
1:Pos/Prs
2:Pos
Learn Answer
Only for Command Set = PM, PMV2
0:Immediatelly
1:Learn End
Command t Mode
Only for Command Set = PM, PMV2
0:Without Ramp Time
1:With Ramp Time
Tylan M1
Only for Command Set = Tylan, Tylan Type 2
0:None
1:Gain Factor/P-Gain
Tylan X1
Only for Command Set = Tylan, Tylan Type 2
0:None
1:Ramp Time/I-Gain
Tylan J3
Only for Command Set = Tylan, Tylan Type 2
0:None
1:Restart
Tylan V
Only for Command Set = Tylan Type 1, Type 2
0:None
1:Pressure Control Selector
Compound
Commands
1[20]
A10A0100
UINT32
RW
NV
Parameter compilation for set and/or get several
Parameters with one command
Array of 20 Parameters
2[20]
A10A0101
UINT32
RW
NV
3[20]
A10A0102
UINT32
RW
NV
4[20]
A10A0103
UINT32
RW
NV