Series 613
OPERATION
984360EC
Edition 12.08.2022
87/149
6.1
Access Mode
6.1.1
Overview
Defines whether the interface or the CPA via the service port has the rights to control the valve
Location: CPA/Parameters System
Access Mode
Control Permission Comment
Local
CPA
Remote
INTERFACE Master
CPA can switch to Local
Locked
INTERFACE Master
CPA can’t switch to Local
Power On state is ‘Remote’
6.1.2
Remote and Locked operation
This product is equipped with an interface to allow for remote operation.
See section «Interface» for details.
'Control Performance Analyzer' software may be used for monitoring during remote control.
In case ‘Control Performance Analyzer’ is used, make sure ‘Remote’ button is
pushed to enable for remote operation.
6.1.3
Local operation
Local operation means that the valve is operated via the service port using a computer.
You can use our software 'Control Performance Analyzer' for Local operation, which is integrated in
the controller. The software is beneficial especially for setup, testing and maintenance.
When communication to service port is interrupted the valve will change to remote
operation. So when service cable will be disconnected or software will be shut down,
the valve returns automatically to remote operation. This may result in an immediate
movement of the valve depending on remote control.