INSTALLATION
Series 613
36/149
Edition 12.08.2022
984360EC
5.10.3
Warning/Error
Location: CPA/Parameters: System.Warning/Error
Parameter
Description
Warning Bitmap
Bit
Hex
Description
0
1
No Learn Data
1
2
Isolation valve does not work
2
4
No Sensor Active
3
8
PFO Not Ready
4
16
Cluster Slave Offline
6
40
Fieldbus Data Not Valid
8
256
Compressed Air Not Falling when valve close
9
512
Compressed Air Too Low
10
1024
Compressed Air Too High
12
4096
Fan stall alarm
Error Bitmap
Bit
Hex
Description
0
1
Homing Position Error
1
2
Homing Not Running
2
4
Homing Error State
3
8
Operation Position Error
4
10
Operation Not Running
5
20
Operation Error State
12
1000
Other Component
30
40000000
General
31
80000000
Internal
Error Number
Refer to Error Number in Troubleshooting
Error Code
Refer to Error Code in Troubleshooting
5.10.4
Service
5.10.4.1
Restart, Error Recovery
Location: CPA/Parameters: System.Services
Parameter
Description
Restart Controller
Emulates a power cycle of the valve
Error Recovery
Attempts to reset the Control Mode Error without
restarting the valves
5.10.4.2
Settings Handling
Location: CPA/Parameters: System.Services.Store/Restore Settings
Parameter
Description
Store User Parameters
Emulates a power cycle of the valve
Restore User Parameters
Attempts to reset the Control Mode Error without
restarting the valves
Restore Factory Parameters
Protective function against changing the settings.
If TRUE, the settings can no longer be changed.
Location: CPA/Parameters: System.Services.Configuration Lock
Parameter
Description
Configuration Lock Mode
Protective function against changing the settings.
If TRUE, the settings can no longer be changed.