Series 613
OPERATION
984360EC
Edition 12.08.2022
95/149
Parameters Executing
Location: CPA/Navigation/Parameters: Pressure Control.Adaptive Learn
Parameter
Description
Start Learn
Starts the learn
Type
Standard
A positioning sequence is executed and various measured
values are recorded in the process.
Short
Opens the valve and measures the pumping speed.
Information about flow and volume is required.
Calculated
Calculated the learn data with the pumping speed
information.
Short or Calculated can be used when there is no way to set a constant
gas flow.
Bank Selection
Select one of four learn bank to place the result of the learn procedure.
Note: Be sure pressure controller select this learn bank!
Pressure Limit [SFS]
Limit pressure to which pressure the learn shall be executed.
The value is related to the sensor full scale of high sensor.
1.0 means the whole pressure range of the sensors
Pressure Limit
Same value as above but in Pressure Unit
Open Speed
Define the speed for opening the valve during the learn procedure.
May be necessary to prevent a pump from crashing.
1.0 means full speed
Status
State of the current learn
0: Not Started
1: In Progress
2: Completed Successfully
3: Aborted
4: Failed
Warning Info
Warning of current learn procedure:
Bit 0: Learn is running
Bit 1: Checksum error (learn data corrupt)
Bit 2: Learn procedure terminated by user
Bit 3: Pressure at position open > 50% of pressure limit
Bit 4: Pressure at minimal conductance position < 10 % of pressure limit
Bit 5: Pressure falls while move valve in direction of close
Bit 6: Pressure at open position does not match pressure of previous open
Bit 7: Learn procedure terminated by program
Bit 8: Pressure <= 0 at open position (no gas flow set?)
Sort Learn Parameter
Parameter
Description
Chamber Volume
Volume above the valve plate in Liter
Gas Flow
Gas flow during the short learn, must be constant during the short learn
Gas Flow Unit
Gas flow unit for above Gas Flow
Pumping Speed
Resulting pumping speed
Calculated Learn Parameter
Parameter
Description
Pumping Speed
Set pumping speed to calculate the learn data