32
Installation and maintenance manual atmoCRAFT
7.2
Overview of the adjustable installation
parameters
The following parameters can be adjusted to match the
unit to the heating system and to the requirements of
the customer:
Note!
In the last column you can enter your settings
after you have set the installation-specific
parameters.
Display
Meaning
Adjustable
values
Factory
setting
Installation-
specific
adjustment
d.00
Test operation on 1st burner stage for gas setting
(only for 2-stage boilers)
0 - Normal operation
(both stages)
1 - After start changes back to 1st
stage
2 - Full capacity (2nd stage)
0
d.01
Heating pump overrun
Starts after ending of heat demand
5 - 60 min
“–” for through flowing
5 mins
d.02
Burner locking time
Starts after ending of heating operation
2 - 60 min
2 min
d.05
Supply temperature target value
Display in °C
–
d.16
Changeover external pump/solar pump
2 = Normal mode
2
d.46
External temperature correction value
For correction of external heat effects on the sensor
- 10 ... 10 K
0 K
d.50
Switch-off hysteresis of feed controller
Switch-off temperature above the calculated target value
0 ... 10 K
6 K
d.51
Switch-on hysteresis of feed controller
Switch-on temperature below the calculated target value
0 ... 10 K
2 K
d.71
Maximum feed temperature for heating operation
40 °C ... 85 °C
75 °C
d.72
Pump overrun time after storage tank charging
0, 10, 20, ... 600 s
300 s
d.75
Maximum storage tank charging time of a
storage tank without its own controller
20, 21, 22 ... 90 min
30 min
d.78
Feed target temperature in storage tank operation
(Limiting of storage tank charging temperature)
60 °C ... 90 °C
90 °C
d.84
Number of hours to the next maintenance or “Off” 0
0 ... 300 x 10 h or “-” (Off)
“-” (Off)
d.85
Minimum feed target temperature
30 °C ... 50 °C
35 °C
Table 7.1 Adjustable parameters of the DIA system