background image

Warning:

 Use only water or an 

appropriate antifreeze. Do not use any 
other liquids especially methanol, 
automotive antifreeze or any kind of oil.
Do not exceed 50% antifreeze.

LION

BOILERS

CEB Series Boiler

Installation Manual

TM

CEB V12.0

Printed in Canada

Summary of Contents for CEB Series

Page 1: ... an appropriate antifreeze Do not use any other liquids especially methanol automotive antifreeze or any kind of oil Do not exceed 50 antifreeze LION BOILERS CEB Series Boiler Installation Manual TM CEB V12 0 Printed in Canada ...

Page 2: ...2 ...

Page 3: ... single phase power to terminals L1 and L2 and connection of a neutral conductor to the N terminal see Fig 4 Three phase models require connection of three phase power of the correct voltage to the L1 L2 and L3 terminals and a 120 volt 15 amp supply to the terminals SL and SN see Fig 5 Introduction Your Electric Boiler has been designed to exacting specifications to provide controlled efficient he...

Page 4: ...25 208 3 31 2 40 32 CEB 208 15 14 7 208 3 40 8 60 48 CEB 208 22 22 5 208 3 62 5 100 80 CEB 208 30 29 4 208 3 81 6 125 100 CEB 600 9 9 600 3 8 7 15 12 CEB 600 15 14 7 600 3 14 1 20 16 CEB 600 18 18 600 4 17 3 30 24 CEB 600 24 23 7 600 5 22 8 30 24 CEB 600 30 29 4 600 3 28 3 40 32 Control Voltage 24 Volts AC Tank Capacity Approx 2 Gallons Shipping Weight about 85 pounds Inlet and Outlet pipe size 1 ...

Page 5: ...sure will decrease at a rate of 0 433 psi per foot above the fill point An expansion tank must be included to allow for approximately 4 expansion of the water in the entire heating system As the water in the system is heated the pressure will increase but a properly sized expansion tank will prevent the pressure from exceeding the recommended operating pressure The radiators or floor system should...

Page 6: ...suitable for floor or wall mount only faces indicated as Zero Clearance may be mounted against combustible surfaces 5 Units must be mounted straight as shown in Fig 2 with the outlet at the top and the inlet on the bottom See Up Arrow on label on side of boiler 6 The circulation pump should be connected to the outlet side of the boiler see Fig 3 Mechanical Installation 1 Refer to Fig 3 for a typic...

Page 7: ...it as the boiler to prevent the pump from being turned off while the boiler is still powered Thermostat Connection The thermostat connection is 24 volt AC Only connect the thermostat after all other work is complete and the entire heating system is thoroughly purged of air The thermostat is connected to the terminals T1 and T2 on the control circuit board see Fig 4 and Fig 5 In zoned systems the e...

Page 8: ...cially true in the spring and fall when it is not so cold outside The actual temperature setting you need to set it to will be determined by the type of heating system the boiler is installed in The range of the aquastat is from 70 to 180º F Start Up A new system must be thoroughly cleaned flushed and drained then refilled with clean water Foreign material circulating through the system could be d...

Page 9: ... Check all valves Check for flow stoppage or air locks Boiler rapid cycles Check anticipator setting Check pump circulation Boiler operates continuously Check anticipator setting Boiler noisy Oversized pump Flow rate too high Flow rate too low Pump location incorrect Boiler not heating enough Insufficient capacity Burnt Elements Flow rate too low Pressure too high Defective expansion tank Defectiv...

Page 10: ...e that Boiler The obligation of the Manufacturer to repair replace or refund the purchase price exists provided the defective part or complete unit is returned to the Manufacturer ANY AND ALL TRANSPORTATION COSTS WILL BE BORNE BY THE PURCHASER Repair replacement or refund of any defective part or unit shall be considered as complete fulfillment of this warranty THIS WARRANTY DOES NOT APPLY TO 1 La...

Page 11: ...FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY THE MANUFACTURER S LIABILITY ON ANY CLAIM OF ANY KIND INCLUDING NEGLIGENCE WITH RESPECT TO THE GOODS OR SERVICES COVERED HEREUNDER SHALL IN NO WAY EXCEED THE PURCHASE PRICE OF THE BOILER OR PART THEREOF WHICH GIVES RISE TO THE CLAIM IN NO EVENT SHALL THE MANUFACTURER BE LIABLE FOR SPECIAL INCIDENTAL INDI...

Page 12: ...12 ...

Page 13: ...13 ...

Page 14: ...14 ...

Page 15: ...15 ...

Page 16: ...16 ...

Page 17: ...17 ...

Page 18: ...at any of the elements then the element relay for that element is stuck on and needs to be replaced 2 Check the fuse on models equipped with a fuse a Remove the fuse located inside the boiler Check it for continuity Replace with a new fuse of the correct type if necessary b Otherwise replace the existing fuse 3 Check that there is 24 volt AC power on the secondary side of the transformer This is w...

Page 19: ...f the element relay indicator lights come on but the power relays do not come on then the low water cut off or the high limit control may be preventing them from coming on This may be due to a faulty component or may be an actual low water or high temperature condition A faulty low water cut off will prevent both the low water indicator and the high limit indicator lights from coming on A faulty h...

Page 20: ...nts but no heat then with the all the power disconnected to the boiler check the resistance of each element with an ohm meter to see if is correct Replace any elements as necessary If the element is open circuit and the cause is unknown it is advisable to also change the relay connected to that element If you have gone through the above steps and the boiler is still not working please contact us f...

Reviews: