Description
of
Function
Codes
VDF730
User
Manual
-
128
-
Function
Code
Parameter
Name
Setting
Range
Default
P5
-
02
JOG
deceleration
time
0
.
0
–
300
.
0s
20
.
0s
These
parameters
are
used
to
defne
the
set
frequency
and
acceleration
/
deceleration
time
of the AC drive when
jogging
.
The
startup
mode
is
"
Direct
start
" (
P4
-
00
=
0
)
and
the stop
mode
is
"
Decelerate
to
stop
" (
P4
-
10
=
0
)
during
jogging
.
P5
-
01
(
JOG
acceleration
time
)
specifes
the
time
for
the
AC
drive
to
accelerate
from
0
Hz
to
the
maximum
output
frequency
(
P0
-
04
).
P5
-
02
(
JOG
deceleration
time
)
specifes
the
time
for
the
AC
drive
to
decelerate
from
the
maximum
output
frequency
(
P0
-
04
)
to
0
Hz
.
Forward
JOG
and
reverse
JOG
are
valid
regardless
of
the
setting
of
P0
-
00
.
Note that
the
JOG
running
frequency
is
not
limited
by the frequency lower limit and
jump
frequency
.
Function
Code
Parameter
Name
Setting
Range
Default
P5
-
03
JOG
during
running
0
:
Disabled
1
:
Enabled
0
It
is
used
to
set
whether
JOG
is
allowed
during
running
.
If the JOG function is enabled during running
,
the AC drive executes the active JOG
command
frst
and
then
restores
to
the
running
state
before
the
JOG
operation
.
Note
that
this
function
is
disabled
during
DC
braking
.
If
the
PLC
is used
,
it
memorizes the running
stage and accumulative running time at the
JOG
moment
.
After the
JOG
operation is completed
,
the AC drive restores to the
running
stage
and
continues
to
run
for
the
rest
time
in
this
stage
.
Function
Code
Parameter
Name
Setting
Range
Default
P5
-
04
Acceleration
time
2
0
.
0
–
300
.
0s
(
m
)
Model
dependent
P5
-
05
Deceleration
time
2
0
.
0
–
300
.
0s
(
m
)
Model
dependent
This group of acceleration
/
deceleration time is set in the same way as acceleration
/
deceleration 1 in P0
-
09 and P0
-
10
.
You can switch over between the four groups of
acceleration
/
deceleration
time
through
a
DI
.
For
more
details
,
see
the
descriptions
of
P2
-
00
to
P2
-
04
.
Function
Code
Parameter
Name
Setting
Range
Default
P5
-
06
Jump
frequency
0
.
00
Hz
to
maximum
frequency
(
P0
-
04
)
0
.
00
Hz
P5
-
07
Frequency
jump
amplitude
0
.
00
Hz
to
maximum
frequency
(
P0
-
04
)
0
.
00
Hz
If
the
set
frequency
is
within
the
frequency
jump
range
,
the
actual
running
frequency
is
the
jump
frequency
close
to
the
set frequency
.
Setting
the jump
frequency helps to
avoid the
mechanical
resonance
point
of
the
load
.
If
the
jump
frequency
is
set
to
0
,
the
frequency
jump
function
is
disabled
.
The principle of the
jump
frequencies
and
jump
amplitude
is
shown
in
the
following
fgure
.
Содержание VDF730 Series
Страница 1: ...VDF730 Series...
Страница 7: ......
Страница 8: ...1 Safety Information and Precautions...
Страница 15: ...Safety Information and Precautions VDF730 User Manual 14...
Страница 16: ...2 Product Information...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 51: ...Mechanical and Electrical Installation VDF730 User Manual 50...
Страница 52: ...4 Operation and Display...
Страница 75: ...Operation and Display VDF730 User Manual 74...
Страница 76: ...5 Function Code Table...
Страница 97: ...Function Code Table VDF730 User Manual 96...
Страница 98: ...6 Description of Function Codes...
Страница 153: ...Description of Function Codes VDF730 User Manual 152...
Страница 154: ...7 EMC...
Страница 158: ...8 Troubleshooting...
Страница 165: ...Troubleshooting VDF730 User Manual 164...