VDF730
User
Manual Mechanical
and
Electrical
Installation
-
49
-
■
Wiring
of
Control
Circuit
Terminals
1
)
Wiring
of
AI
terminals
Weak analog voltage signals are easy to suffer external interference
,
and therefore the
shielded cable must be used and the cable length
must be less than
20 m
,
as shown in
following
fgure
.
Figure
3
-
24
Wiring
mode
of
AI
terminals
+
10 V
AI1
GND
Potentiometer
PE
<
20 m
VDF730
In
applications
where
the
analog
signal
suffers
severe
interference
,
install
the
flter
capacitor
or
ferrite
magnetic
core
at
the
analog
signal
source
.
Figure
3
-
25
Wiring
of
AI
terminals
in
special
scenarios
AI1
GND
Cross
or
wind
two
or three
coils
in
the
same
direction
0
.
022
uF
,
50
V
Ferrite
magnetic
core
C
VDF730
Содержание VDF730 Series
Страница 1: ...VDF730 Series...
Страница 7: ......
Страница 8: ...1 Safety Information and Precautions...
Страница 15: ...Safety Information and Precautions VDF730 User Manual 14...
Страница 16: ...2 Product Information...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 51: ...Mechanical and Electrical Installation VDF730 User Manual 50...
Страница 52: ...4 Operation and Display...
Страница 75: ...Operation and Display VDF730 User Manual 74...
Страница 76: ...5 Function Code Table...
Страница 97: ...Function Code Table VDF730 User Manual 96...
Страница 98: ...6 Description of Function Codes...
Страница 153: ...Description of Function Codes VDF730 User Manual 152...
Страница 154: ...7 EMC...
Страница 158: ...8 Troubleshooting...
Страница 165: ...Troubleshooting VDF730 User Manual 164...