Mechanical
and
Electrical
Installation
VDF730
User
Manual
-
46
-
requirement
.
The specification and installation method of external power cables
must
comply
with
the
local
safety
regulations
and
related
IEC
standards
.
–
Use copper conductors of a proper size as power cables according to the
recommended
values
in
section
8
.
3
.
2
)
DC
bus
terminals
(+), (-)
–
Terminals
(+)
and
(-)
of DC bus have residual voltage
after
power
-
off
.
Do
not
touch
them
before
ensuring
that
the
CHARGE
indicator
becomes
off
and
the
voltage
is
less
than
36
V
.
Otherwise
,
you
may
get
electric
shock
.
–
When
connecting
the
external
braking
unit
for
the
AC
drive
of
37
kW
or
above
,
do
not reverse poles
(+)
and
(-).
Otherwise
,
it may damage
the AC
drive
and
even
cause
a
fre
.
–
The
cable
length
of
the
braking
unit
must
not
exceed
5
m
.
Use
twisted
pair
wire
or
pair
wires
for
parallel
connection
.
–
Do not connect the braking resistor directly to the DC bus
.
Otherwise
,
it may
damage
the
AC
drive
and
even
cause
a
fre
.
3
)
Terminals
(+),
PB
for
connecting
the
braking
resistor
–
The connecting terminals of the braking resistor are effective only for the AC
drives
confgured
with
a
built
-
in
braking
unit
.
–
The cable
length of
the
braking
resistor
must
be
smaller
than
5
m
.
Otherwise
,
it
may
damage
the
AC
drive
.
4
)
Terminals
P
, (+)
for
connecting
the
external
reactor
For
the
AC
drives of 75G
/
90P
and above
,
remove
the jumper
bar
across terminals
P
and
(+)
and
install
the
reactor
between
the
two
terminals
.
5
)
AC
drive
output
terminals
U
,
V
,
W
–
The
capacitor
or
surge
absorber
must
not
be
connected
to
the
output
side
of
the
AC drive
.
Otherwise
,
it
may cause
frequent AC
drive faults
or even damage the
AC
drive
.
–
If the motor cable is too long
,
electrical resonance will be generated due to
the impact of distributed capacitance
.
This will damage the motor insulation or
generate
higher
leakage
current
,
thus
causing
the
AC
drive
to
trip
in
overcurrent
protection
.
If the motor cable is greater than 100 m long
,
an AC output reactor
must
be
installed
close
to
the
AC
drive
.
6
)
Terminal
PE
–
This
terminal
must be grounded reliably
.
The resistance of the grounding cable
must
be
less
than
0
.
1
Ω.
Otherwise
,
it
may
cause
fault
or
damage
to
the
AC
drive
.
–
Do
not
connect
the
earthing
terminal
to
the
neutral
conductor
of
the
power
supply
.
–
The
impedance of the PE conductor
must be able to withstand the
large
short
-
circuit
current
that
may
arise
when
a
fault
occurs
.
–
Select
the
size
of
the
PE
conductor
according
to
the
following
table
.
Содержание VDF730 Series
Страница 1: ...VDF730 Series...
Страница 7: ......
Страница 8: ...1 Safety Information and Precautions...
Страница 15: ...Safety Information and Precautions VDF730 User Manual 14...
Страница 16: ...2 Product Information...
Страница 30: ...3 Mechanical and Electrical Installation...
Страница 51: ...Mechanical and Electrical Installation VDF730 User Manual 50...
Страница 52: ...4 Operation and Display...
Страница 75: ...Operation and Display VDF730 User Manual 74...
Страница 76: ...5 Function Code Table...
Страница 97: ...Function Code Table VDF730 User Manual 96...
Страница 98: ...6 Description of Function Codes...
Страница 153: ...Description of Function Codes VDF730 User Manual 152...
Страница 154: ...7 EMC...
Страница 158: ...8 Troubleshooting...
Страница 165: ...Troubleshooting VDF730 User Manual 164...