ELECTRICAL CABLING AND CONNECTIONS
vacon • 91
24-hour s358 (0)40 837 1150 • Email: [email protected]
6
X10
UH
UL
VH
VL
W H
W L
ASIC boa rd
DC- DC+
X6
X3 X4 X5
X29
X9
X15
X26
H1H2H3H4H5H6H7
H1
H2
H3
H4
H5
H6
H7
X1
X2
X3
H7
H6
H5
H4
H3
H2
H1
X1
X2 X3
Figure 6-23. Optical cable adapter board
Optical terminals on Optical cable adapter board:
H1
Gate control enable
H2
Phase U control
H3
Phase V control
H4
Phase W control
H5
ADC synchronization
H6
VaconBus data from control board to ASIC
H7
VaconBus data from ASIC to control board
Other terminals on adapter board:
X1
Control board connection
X2
Supply voltage 24Vin (from power unit ASIC)
X3
Supply voltage 24Vin (customer);
•
Max. current 1A
•
Terminal #1: +
•
Terminal #2: –
Note: The minimum optical cable bending radius is 50 mm.
Note: Terminals
X2
and
X3
can be in use simultaneously. However, if the +24V supply from the control I/O
terminals (e.g. from board OPT-A1) is used, this terminal must be protected with a diode.