ELECTRICAL CABLING AND CONNECTIONS
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
6
6.3.3
Connections between mains device and inverter power module
The dimensions in the table below shall be taken into account if some kind of mains device (e.g. fuse,
switch fuse, contactor) is used in the input line between the mains and the Vacon Liquid-Cooled inverter.
Connection
Chassis
Type
Conductor
cross section
[mm
2
]
Busbar size
(flexible con-
nection)
Busbar size
(bright Cu)
0016_5
0022_5
CH3
0031_5
6
0038_5
0045_5
CH3
0061_5
10
0072_5
0087_5
CH4
0105_5
25
CH4 0140_5
50
CH5 0168_5
70
CH5 0208_5
95
CH5 0261_5 120
2*24*1
CH61 0300_5
CH61 0385_5
2*70
CH72 0460_5 2*95
CH72 0520_5 2*120
1*50*5
CH72 0590_5 2*150
5*32*1
CH72 0650_5
CH72 0730_5
1*80*5
CH63 0820_5
CH63 0920_5
CH63 1030_5
CH63 1150_5
2*(6*40*1)
1*100*5
CH74 1370_5
CH74 1640_5
2*100*5
CH74 2060_5
CH74 2300_5
3*100*5
Table 6-17. Connections from mains device to drive