EU DIRECTIVE
vacon • 11
24-hour s358 (0)40 837 1150 • Email: [email protected]
2
2.2.3.1
IT networks
The grounding of input capacitors made by default with the grounding screw at terminal X41 of the bus
board in all drives is imperative in all variations of TN/TT networks. Should the drive be used in IT net-
works, the screw at X41 must be removed. It is strongly recommended that this be done by Vacon per-
sonnel. Ask you local distributor for more information.
2.2.4
Manufacturer's declaration of conformity
The following pages present the Manufacturer's Declarations of Conformity assuring the compliance of
Vacon frequency converters with the EMC-directives.