74 • vacon
ELECTRICAL CABLING AND CONNECTIONS
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
6
A
B
nxw6.fh8
6.1.5
Installation space
Enough free space shall be left above and below the frequency
converter/inverter to ensure practical and appropriate electrical and
cooling connections. The minimum dimensions are given in the table
below. The space left and right to the drive may be 0 mm.
Chassis A
[mm]
B
[mm]
CH3 100 150
CH4 100 200
CH5 100 200
CH61 100 300
CH62 100 400*
CH63 200 400*
CH64 200 500*
CH72 200 400*
CH74 200 500*
Table 6-15. Installation space
*Distance to the cable connection
block. Additional space must be re-
served for possibly used ferrite rings.
See chapter 6.1.1.2.