102 • vacon
CONTROL KEYPAD
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
7
7.3.3
Keypad control menu (M3)
In the
Keypad Controls Menu
, you can choose the control place, edit the frequency reference and change
the direction of the motor. Enter the submenu level with the
Code
Parameter
Min
Max
Unit
Default
Cust
ID
Note
P3.1 Control
place 1
3
1
125
1=I/O terminal
2=Keypad
3=Fieldbus
R3.2 Keypad
reference
Par.
2.1.1
Par. 2.1.2
Hz
P3.3
Direction (on keypad)
0
1
0
123
0=Forward
1=Reverse
R3.4 Stop
button 0 1 1
114
0=Limited function of Stop
button
1=Stop button always en-
abled
Table 7-2. Keypad control parameters, M3
7.3.3.1
Selection of control place
There are three different places (sources) which the frequency converter can be controlled from. For each
control place, a different symbol will appear on the alphanumeric display:
Control place
Symbol
I/O terminals
Keypad (panel)
Fieldbus
Change the control place by entering the edit mode with the
. The options can then be
browsed through with the
. Select the desired control place with the
diagram on the next page.
Figure 7-6. Selection of control place
I/O term
Keypad
Bus/Comm
P1
Î
P4
READY
I /Oterm
READY
I/ Oterm
READY
I/ Oterm
READY
I/ Oterm
enter
READY
Keypad
STOP
STOP
STOP
STOP
STOP
Keypad control
Control Place
I/O Remote
Control Place
I/O Remote
Control Place
Keypad
Control Place
Keypad