110 • vacon
CONTROL KEYPAD
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
7
7.3.4.3
Fault time data record
When a fault occurs the information described above in 7.3.4 is displayed. By pushing the
here you will enter the
Fault time data record menu
indicated by T.1
Æ
T.13. In this menu, some se-
lected important data valid at the time of the fault are recorded. This feature is intended to help the user or
the service person to determine the cause of fault.
The data available are:
T.1
Counted operation days
(Fault 43: Additional code)
d
T.2
Counted operation hours
(Fault 43: Counted operation days)
hh:mm:ss
(d)
T.3
Output frequency
(Fault 43: Counted operation hours)
Hz
(hh:mm:ss
)
T.4
Motor current
A
T.5
Motor voltage
V
T.6
Motor power
%
T.7
Motor torque
%
T.8
DC voltage
V
T.9
Unit temperature
°
C
T.10
Run status
T.11
Direction
T.12
Warnings
T.13
0-speed*
Table 7-5. Fault time recorded data
* Tells the user if the drive was at zero speed (< 0.01 Hz) when the fault occurred
Real time record
If real time is set to run on the frequency converter the data items T1 and T2 will appear as follows:
T.1
Counted operation days
yyyy-mm-dd
T.2
Counted operation hours
hh:mm:ss,
sss