RUN
FAULT
READY
*)
*)
Reference output
+10 Vref
Terminal
Standard I/O board
Signal
1
24V auxiliary voltage
24Vout
6
Analogue input,
voltage or current
Reference
potentiometer
1...10kΩ
Actual value
2-wire transmitter
I = (0)4...20mA
AI1+
2
Analogue input
common, (current)
AI1-
3
Analogue input,
voltage or current
AI2+
4
Analogue input
common, (current)
AI2-
5
Analogue signal
(+output)
AO1+
RUN
18
Analogue output
common / I/O ground
AO1-/GND
19
24V auxiliary
input voltage
+24Vin
30
24V auxiliary voltage
24Vout
12
I/O ground
GND
7
I/O ground
GND
13
Digital input 1
DI1
8
Digital input 2
DI2
9
Digital input 3
DI3
10
Digital input 4
DI4
14
Digital input 5
DI5
15
Digital input 6
DI6
16
Relay output 1
RO1 NC
21
22
RO1 CM
RO1 NO
23
Common for DI1-DI6
CM
11
Common for DI1-DI6
CM
17
Serial bus, negative
RS485
A
Serial bus, positive
RS485
B
Relay output 2
Relay output 3
RO2 NC
24
25
RO2 CM
RO2 NO
26
32
RO3 CM
RO3 NO
33
Description
Frequency reference
Frequency reference
Start forward
Start reverse
External fault
DI4
DI5
Freq. ref.
Open
Closed
Open
Closed
Open
Open
Closed
Closed
Analog input 1
Preset Freq. 1
Preset Freq. 2
Preset Freq. 3
Fault reset
Output frequency
Modbus RTU
BACnet, N2
mA
Fig. 39: The signals of the control terminals on the standard I/O board, and a connection example.
If you include the optional code +SBF4 in your order, the relay output 3 is replaced with a
thermistor input.
VACON · 92
CONTROL UNIT
6
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Содержание 100 flow
Страница 1: ...vacon 100 vacon 100 flow vacon 100 hvac ac drives installation manual wall mounted drives ...
Страница 2: ......
Страница 4: ...VACON 4 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 78: ...3 Remove the cable cover M4x8 MR8 M4x8 MR9 VACON 78 POWER CABLING 5 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...