Table 19: The cable and fuse sizes for Vacon
®
100 in North America, mains voltage 525-690 V
Frame
Type
IL [A]
Fuse
(Class T/J)
[A]
Mains, motor
and brake
resistor*
cable Cu
[AWG]
Terminal cable size
Mains cable
terminal [AWG]
Grounding
terminal [AWG]
MR5 (600
V)
0004 6
3.9
6
14
20-5
17-8
0006 6
6.1
10
14
20-5
17-8
0009 6
9.0
10
14
20-5
17-8
0011 6
11.0
15
14
20-5
17-8
MR6
0007 7
7.5
10
12
13-0
13-2
0010 7
10.0
15
12
13-0
13-2
0013 7
13.5
20
12
13-0
13-2
0018 6
0018 7
18.0
20
10
13-0
13-2
0022 6
0022 7
22.0
25
10
13-0
13-2
0027 6
0027 7
27.0
30
8
13-0
13-2
0034 6
0034 7
34.0
40
8
13-0
13-2
MR7
0041 6
0041 7
41.0
50
6
9-2/0
9-2/0
0052 6
0052 7
52.0
60
6
9-2/0
9-2/0
0062 6
0062 7
62.0
70
4
9-2/0
9-2/0
MR8
0080 6
0080 7
80.0
90
1/0
1 AWG-350 kcmil 1 AWG-350 kcmil
0100 6
0100 7
100.0
110
1/0
1 AWG-350 kcmil 1 AWG-350 kcmil
0125 6
0125 7
125.0
150
2/0
1 AWG-350 kcmil 1 AWG-350 kcmil
POWER CABLING
VACON · 67
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]
5
Содержание 100 flow
Страница 1: ...vacon 100 vacon 100 flow vacon 100 hvac ac drives installation manual wall mounted drives ...
Страница 2: ......
Страница 4: ...VACON 4 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...
Страница 78: ...3 Remove the cable cover M4x8 MR8 M4x8 MR9 VACON 78 POWER CABLING 5 TEL 358 0 201 2121 FAX 358 0 201 212 205 ...