9
Make sure that the grounding conductor is
connected to the motor and also to the terminals
that are identified with .
a
)
To obey the requirements of the standard EN
61800-5-1, obey the instructions in chapter 2.4
Grounding and earth fault protection.
b
)
If a double grounding is necessary, use the
grounding terminal under the drive. Use an M5
screw and tighten it to 2.0 Nm or 17.7 lb-in.
= M5; 2 Nm
10 Attach again the cable cover and the cover of the
drive.
VACON · 74
POWER CABLING